SunStat Installation Manual

Please be aware local codes may require this control to be
installed or connected by an electrician.
Read this manual BEFORE using this equipment.
Failure to read and follow all safety and
use information can result in death, serious
personal injury, property damage, or damage
to the equipment.
Keep this manual for future reference.
Installation
Location
Items Needed
Box Contents
Features:
Installation must be performed by qualified persons, in accordance
with local codes, ANSI/NFPA 70 (NEC Article 424) and CEC Part 1
Section 62 where applicable. Prior to installation, please consult
the local codes in order to understand what is acceptable. To the
extent this information is not consistent with local codes, the local
codes should be followed. Regardless, electrical wiring is required
from a circuit breaker or other electrical circuit to the control. It
is recommended that an electrician perform these installation
steps. Please be aware local codes may require this product to
be installed by an electrician.
Important Safety Information
This pictorial alerts you to electricity,
electrocution, and shock hazards.
This symbol identifies hazards which, if not
avoided, could result in death or serious injury.
This symbol identifies hazards which, if not
avoided, could result in minor or moderate injury.
This symbol identifies practices, actions, or
failure to act, which could result in property
damage or damage to the equipment.
This is a safety-alert symbol. The safety-alert symbol
is shown alone or used with a signal word (DANGER,
WARNING, or CAUTION), a pictorial and/or a safety
message to identify hazards.
When you see this symbol alone or with a signal word on your
equipment or in this manual, be alert to the potential for death or
serious personal injury.
ALWAYS wire all circuits with insulation rated 600V minimum.
ALWAYS mount this control to a grounded electrical box.
ALWAYS use power supply wires suitable for at least (194°F) 90°C.
ALWAYS seek help if a problem arises. If ever in doubt about the
correct installation procedure to follow, or if the product appears
to be damaged, the factory must be called before proceeding
with the installation.
Floor temperature
control with optional
air-sensing mode
Remote access via
mobile app
Touchscreen display
with multiple color
themes
Easy-to-use programs
and scheduling
Outdoor temperature
and weather display
options
Comprehensive help
screens
3-Year warranty
To prevent the risk of personal injury and/or death,
make sure power is not applied to the product until
it is fully installed and ready for final testing. All work
must be done with power turned off to the circuit
being worked on.
To reduce the risk of electric shock, do not connect to a circuit
operating at more than 150 V to ground.
Power Supply
Pull power supply wiring to the control location.
Leave about 6 to 8" (15 to 20 cm) of wire for connections.
This wiring should be size 12 or 14 AWG, in compliance with
local code requirements.
A qualified person should run a dedicated circuit from the main
circuit breaker panel to the control location. If a dedicated
circuit is not possible, it is acceptable to tap into an existing
circuit. However, there must be enough capacity to handle the
load (amps) of the floor heating system being installed, and any
appliance likely to be used on the circuit such as a hair dryer
or vacuum cleaner.
Avoid circuits that have ballasted lighting, motors, exhaust fans,
or hot tub pumps to reduce the likelihood of interference.
The circuit breaker should be rated 20 amps for total circuit loads
up to 15 amps. A 15-amp circuit breaker may be used for total
circuit loads up to 12 amps.
A GFCI (ground-fault circuit interrupter) or AFCI (arc-fault circuit
interrupter) type circuit breaker may be used, but is not necessary.
Thermostat Wiring
Before connecting the wires to the back of the thermostat,
detach the display front from the base.
Bottom Plate Work
Drill or chisel holes at the bottom plate as indicated. One hole
is for routing the power lead conduit and the other is for the
thermostat sensor. These holes should be directly below the
electrical box(es).
Electrical box (must be UL Listed and proper size)
Wire nuts (must be UL Listed and proper size)
Flexible or rigid conduit (if required, must be UL Listed and
proper size)
12-guage or 14-guage electrical wiring cable (UL Listed)
Nail plate
Hot glue gun and hot glue
Thermostat is designed for indoor dry location only.
Do not install where there is a draft, direct sun, hot-water piping,
ducting or other cause for inaccurate temperature readings.
Do not install where there is electrical interference from
equipment, appliances, or other sources.
Install away from all water sources such as sinks and at least
4' (1.2 m) away from showers and bathtubs.
Consider easy access for wiring, viewing, and adjusting.
Install at a suitable height, normally about 4-1/2' to 5' (1.4 m
to 1.5 m) from the floor.
SunStat Connect Wi-Fi thermostat
Floor sensor
Screwdriver
Installation manual
2 machine screws
5 wire nuts
This device complies with Part 15 of the FCC Rules and with Industry Canada
license-exempt RSS standard(s). Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that
may cause undesired operation.
Changes or modifications not expressly approved by the party responsible
for compliance could void the user’s authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates uses and can radiate
radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one of
the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Consult the dealer or an experienced radio/TV technician for help.
Make sure 120 VAC is supplied to 120 VAC cables and 240
VAC is supplied to 240 VAC mat or wire. Otherwise, dangerous
overheating and a fire hazard could result. Do not exceed
15-amps on this control.
SunStat
®
Connect
Installation and
Operation Manual
58
°F
74
°F
Floor
Smart Start
Outdoor
6:27Fri, May 01
AM
HEATING
TESTRESET
GFCI / TEST MONTHLY
The following cautions must be observed:
SunStat Sensor Installation
The SunStat sensor can be installed with or without electrical
conduit depending on code requirements. Conduit is recommended
for added protection against nails and screws.
Do not place the sensor in the same conduit as the power leads
to avoid possible interference. Open a separate knock-out in the
bottom of the thermostat box. Feed the sensor (and conduit, if
used) through the knock-out, down through the cut-out in the
bottom plate, and out into the floor where the heating cable will
be installed.
If the sensor wire needs to be secured to the wall stud, wait
until after the wire or mat and sensor are completely installed
on the floor.
At the sensor location, measure at least 1' into the heated area.
Mark the spot where the sensor will be attached to the floor. Be
sure to place the sensor exactly between two of the heating wires.
Ensure the sensor wire does not cross over any heating wires.
Do not locate the sensor outside the heating area or in a gap
between heating wires that is wider than the rest of the floor.
Do not locate the sensor where direct sun, hot-water piping,
heat duct, or lighting below will cause inaccurate temperature
reading. Do not locate the sensor where an insulating item such
as a rug is likely to be placed.
To make sure the sensor tip does not create a high spot in the
floor, it may be necessary to chisel a channel into the floor and
lay the sensor tip into the channel. Hot glue the tip into place.
Do not cut the sensor wire or remove the black cable protector.
Strip the wire ends to 1/8" long.
Floor Heating Mat or Cable Power Lead Installation
The shielded power lead can be installed with or without electrical
conduit (recommended for added protection against nails or
screws), depending on code requirements.
Remove one of the knock-outs in the electrical box to route the power
lead. If electrical conduit is not required by code, install a wire collar to
secure the power leads where they enter the box. If conduit is required
by code, install 1/2" (minimum) conduit from the bottom plate up to the
electrical box. For multiple power leads (multiple cables), install
3/4" conduit.
Secure a steel nail plate over the cutout in the bottom plate to
protect the wires against baseboard nails later.
SunStat Relay Rough-in Wiring
A SunStat Relay C3 is used when more than 15 amps must be
controlled by one SunStat thermostat. The SunStat Connect is only
compatible with the SunStat Relay C3. Do not use other models.
Pull 18 AWG to 24 AWG 2-conductor shielded wire from the
relay location to this control location. The wire may be up to
100' (30 m) long.
Strip the wire ends to 1/8" long.
Refer to the instructions provided with the SunStat Relay C3 for
additional details.
Home Automation System Rough-in Wiring
A short or 24 VAC applied between the Away and Com terminal
will switch the thermostat between the 'Away' temperature and
regular operation.
Pull 18 AWG to 24 AWG 2-conductor shielded wire from the home
automation control to this control location.
Strip the wire ends to 1/8" long.
Power lead
conduit
Wire
clip
Power
lead
Sensor wire
Sensor wire
For retrofit installations, cut
out drywall and chisel out the
bottom plate to route wires to
control.
Sensor, relay and home automation connections are made to the
terminal block by inserting the wires into the square openings
and tightening the screws on the side.
Connect the sensor wires to the SENSOR terminals on the
thermostat. These connections are not polarity sensitive.
For a SunStat Relay C3, connect 2 wires from the relay to the
Com and Relay terminals on the thermostat. Ensure the Com
wire at the relay is the same conductor connected to the Com
terminal on the thermostat.
Connect the Away and Com terminals to the appropriate
conductors from a home automation system. Refer to the
instructions for the home automation control before making
these connections.
Designed and
assembled in Canada
E365015
Temp. Ind. &
Reg. Equip.
L1
L
LOAD 1
1
2
3
4
5
6
SENSOR
SENSOR
RELAY(B)
COM (A)
AWAY
MAY 2015
1079-01
GFCI CLASS A
L2
N
LOAD 2
Floor Heating
Floor Heating
Power:
120/240 ±10% V (ac)
60 Hz, 3 W
Load:
120/240 V (ac), 15 A
1800/3600 W
SunStat Connect
(240 V)
(120 V)
(240 V)
(120 V)
Home Auto.
Relay C3
Floor sensor
Mat or
Cable
power
lead
Power
supply
from
breaker
See over for operation details
Finish Thermostat Installation
Ensure all connections are secure.
Carefully press the wires back into the electrical box. Do not
use the control to push them.
Use the included screws to attach the thermostat base to the
electrical box. Do not overtighten.
When re-attaching the display front, line up the top edge with
the base, then rotate the bottom towards the base. Ensure
the pins are not bent when connecting.
Make sure the wire connections are secure by gently tugging
on them. Otherwise, arcing could occur, causing dangerous
overheating and a possible fire hazard. For added security,
overwrap each wire nut connection with electrical tape.
While holding the base
section in one hand,
pull the lower half of the
display front towards
you to pivot it away from
the base.
Specifications:
Power supply 120/240 V (ac), 60 Hz, 3 watts
Maximum load 15 amps, resistive
Maximum power 1800 watts at 120 VAC
3600 watts at 240 VAC
GFCI
Class A (5 milliamp trip)
Approvals UL 943, UL 873, UL 991, FCC
Meets Class B: ICES-003 & FCC Part 15B
Ambient conditions 32°F to 86°F (0 to 30°C), <90% RH non-condensing
Floor Sensor Thermistor, 10k NTC type, 300 V jacketed cable,
15' long
Using the wire nuts included with the thermostat:
Connect the ground wire from the power supply to the ground
wire from the floor heating power lead. If the electrical box is
metal, use a short length of wire to connect ground wires to
the bonding screw.
Connect the white wire labeled LOAD 2 on the thermostat to
the white (or blue for 240 VAC) wire from the heating mat or
cable power lead.
Connect the black wire labeled LOAD 1 on the thermostat
to the black wire from the heating mat or cable power lead.
For 120 VAC connections, the L wire connects to the black (L)
hot conductor from the breaker panel. The N wire connects
to the white (N) neutral conductor.
For 240 VAC connections, the L1 connects to one side of the
240 VAC supply from the breaker panel and the L2 to the other.
Model# 107901, 107902, 107903, 107904, 107905
NEVER forget to install the floor sensor included with the thermostat.
NEVER put the system into full operation until the tile or flooring
installer verifies all cement materials are fully cured (typically two
to four weeks after installation).
ALWAYS use copper supply conductors to the thermostat. Do
not use aluminum.
ALWAYS wire all circuits as Class 1, electric light & power circuits.

Summary of content (2 pages)