Brochure

© S unTou ch
17
208 VAC Cable
Coverage (ft
2
)
3" O.C.
(50 W/ft
2
)
4" O.C.
(38 W/ft
2
)
Length Order# Model# Amps
14 19 55' 81011408 SC50208014 3.4
20 26 78' 81011416 SC50208020 4.8
30 39 118' 81011417 SC50208030 7. 2
35 46 138' 81011418 SC50208035 8.4
40 53 158' 81011383 SC50208040 9.6
45 59 178' 81011384 SC50208045 10.8
55 72 218' 81011385 SC50208055 13.2
60 79 238' 8101138 6 SC50208060 14.4
65 85 257' 81011387 SC50208065 15.6
75 98 297' 81011388 SC50208075 18.0
80 105 317' 81011389 SC50208080 19.2
90 118 357' 8101139 0 SC50208090 21.6
Cable Selection
ProMelt® Cable
240 VAC Cable
Coverage (ft
2
)
3" O.C.
(50 W/ft
2
)
4" O.C.
(38 W/ft
2
)
Length Order# Model# Amps
15 20 59' 81011391 SC50240015 3.1
25 33 98' 8101139 2 SC50240025 5.2
30 39 118' 810113 93 SC50240030 6.3
40 53 158' 8101139 4 SC50240040 8.3
45 59 178' 8101139 5 SC50240045 9.4
55 72 218' 8101139 6 SC50240055 11.5
60 79 238' 81011397 SC50240060 12.5
65 85 257' 8101139 8 SC50240065 13.5
75 98 297' 8101139 9 SC50240075 15.6
80 105 317' 810114 00 SC50240080 16.7
90 118 357' 81011401 SC50240090 18.8
105 137 417' 81011402 SC50240105 21.9
Calculate the required watts per square foot.
Select a spacing option that will provide enough output for the expected
performance of the snow melt system.
Calculate the total area to be melted for each individually controlled zone.
Determine which voltage will be used.
Select a cable long enough to cover the melting area.
277 VAC ProMelt Cables are available via Special Order only. Please allow additional lead time.