ProMelt Installation Manual

15
PM-HSC5 Slab Sensor
STEP 3.9
Use a digital multi-meter to measure the resistance between the conductors and ground wire of the mat/cable power
leads again. Record these resistances in Table 3 under After mat/cable is secured in place.
STEP 3.10
Feed the power leads through the conduit into the junction box, leaving at least 6 inches of free lead length. Secure
the heating cable and splice so that they will not be pulled into the conduit.
Insert a generous amount of electrical conduit sealant into the
conduit end around the power leads to prevent water entry
STEP 3.11
If a slab sensor is being installed, place the sensor socket according
to the instructions included with the sensor. Secure and seal it to
the conduit installed earlier. It should be located halfway between
heating cables and in an area that is recommended by the sensor
manufacturer. Make sure the top of the sensor will be flush with
the surface of the finish layer. Make sure it is protected with a cap
or seal.
STEP 3.12
Take a photo of the mat/cable installation. This can be very helpful
later for utility work, changes to the site, etc. to avoid possible
damage. Keep the photos with this installation manual.
SPECIAL APPLICATIONS
STEP 3.13
Stairs: If you are installing ProMelt Mat onto stairs, carefully cut the tape holding the heating cable. If installing
ProMelt Cable, skip the previous step. Secure a single run of cable to the side of a riser. Lay 3 or 4 runs of cable on the
tread area as needed and continue up each stair. Follow these guidelines:
Lay cable no greater than 3 inches from the front edge of the finished tread. Otherwise this edge may not
snow melt properly.
Lay cable at least 6 inches from the side edges of the finished tread.
Account for future hand railings that could be mounted onto the tread, especially in the middle of a long tread
if required. Use a marker or indicate on drawings where the railing may be installed safely later.
Avoid pinching or sharply bending the cable. At the corner of the riser and tread, keep a minimum 1-inch
radius bend, but secure it flat enough that the surface concrete or pavers will not pinch the cable.
Do not install the mat/cable on or under non-masonry stairs such as wooden or composite construction.
ProMelt Mat on stairs ProMelt Cable on stairs