Install Instructions

11 of 24 © 2015 Watts Radiant
STEP 2.3
Power Lead Conduit
Install a minimum of 3/4" rigid or flexible Listed conduit from the control electrical box or
junction box to the slab location. Extend it 2" to 6" into the slab edge and attach a bushing to
the end to prevent damaging the cable power leads.
STEP 2.4
Sensor Conduit
The SunStat sensor is designed to be embedded in the slab. However, it is recommended that
the sensor be installed in a minimum of 1/2" rigid or flexible Listed conduit for added protection.
If the end of the conduit is sealed, this would allow the sensor to be removed and replaced if
there ever is a problem. Install so that the sensor tip is located 1" below the surface, half-way
between heating cables, and at least 1' into the heated area.
STEP 2.5
Rough-in Wiring
Install appropriate 12 or 14 AWG electrical wire from the circuit breaker or branch circuit
source to the SunStat electrical box (and SunStat Relay box(es) if needed) following all codes,
see Table 5.
If SunStat Relay(s) are used, feed appropriate wire between the SunStat Relay(s) and the
SunStat thermostat. See SunStat Relay instructions for details of wire size and type.
STEP 2.6
Mark the circuit breaker in the panel which feeds the system with “Floor warming/bath” or
similar description.
Splice, not
in conduit
Power
Lead
Heating
Cable
Concrete
slab
Gravel base
Splice, not
in conduit
Power
Lead
Heating
Cable
Insulation
Concrete
slab
Foundation Wall Gravel base