Install Instructions

IOM-WR-SH 1528 20 of 24
Power Lead
From Cable 2
Power Lead
From Cable 1
G
G
Sun Stat
or Relay
SunStat / Relay Connections
SlabHeat Cable
Connections
Power
Supply
(120 VAC or
240 VAC)
Load 1
Line 1
Line 2
Black
Black
White
White
Load 2
Standard NM Cable
(12 or 14 AWG)
Connecting Multiple Cables
Multiple heating cables can be con-
nected to a single SunStat or SunStat
Relay II. Refer to Table 2 and Table 5
for details on calculating the maximum
number of heating cables per control
or relay.
To prevent the risk of personal injury and/or death, do not perform any electrical work unless
qualified to do so. Work should be done with great care and with power turned off to the
circuit being worked on. Follow all local building and electrical codes.
The SunStat is not fully illustrated in these diagrams in order to simplify them. These diagrams
are given only as examples of how to properly connect multiple cables. Care must be taken
not to overfill a box. Be sure to use wire nuts that are the correct size for the connections
being made. Follow all codes for wiring.
All electrical work must be done by a qualified licensed electrician in accordance with local
building and electrical codes, and the National Electrical Code (NEC), especially Article 424
of the NEC, ANSI/NFPA70 and Section 62 of CEC Part 1.