Welcome to ProMelt Electric Snow melting
SunTouch ProMelt products are a simple way to eliminate snow and ice from surfaces. This instruction manual is
provided as a guide to installing ProMelt Mat and ProMelt Cable, including design considerations, mat and cable
installation, control installation, precautions, and surfacing guidelines.
Specifications for ProMelt Mat:
ProMelt Mat is a complete heating mat consisting of a series resistance heating cable and a single power lead for easy
single-point connection. The heating cable is pre-formed into a mat to provide consistent spacing and quick roll-out
installation on the job site. The heating mat length cannot be cut to fit.
Sizes: Widths 2, 3 feet
Lengths 5 up to 56 feet
Voltages: 120, 208, 240, 277 VAC, 1-phase
Watts: 50 W/sqft (170 Btu/h/sqft) and 38 W/sqft (130 Btu/h/sqft)
Maximum heater current: 24 amps
Maximum circuit load: 50 amps
GFCI Class B (ground fault equipment protection) required for each circuit
Listing: ETL Listed for U.S. and Canada under UL 515, IEEE 515.1, and
CAN/CSA C22.2 No. 130-03
Listing file number: 3151992
Application: outdoor use only, embedded in concrete, asphalt, sand (see Step 1.1)
Minimum bend radius: 1 inch
Maximum exposure temperature (continuous and storage): 221°F (105°C)
Maximum exposure temperature (short-term for asphalt covering): 285°F (140°C)
Minimum installation temperature: 40°F (4.5°C)
Specifications for ProMelt Cable:
ProMelt Cable is a complete heating cable consisting of a series resistance heating cable and a single power lead for
easy single-point connection. The heating cable length cannot be cut to fit.
Voltages: 120, 208, 240, 277 VAC, 1-phase
Watts: 50 W/sqft (170 Btu/h/sqft), spaced at 3 inches on-center
38 W/sqft (130 Btu/h/sqft), spaced at 4 inches on-center
(Cable is designed to operate at approximately 12.5 W/linear foot of cable at rated voltage.)
Maximum heater current: 24 amps
Maximum circuit load: 50 amps
GFCI Class B (ground fault equipment protection) required for each circuit
Listing: ETL Listed for U.S. and Canada under UL 515, IEEE 515.1, and CAN/CSA C22.2 No. 130-03
Listing file number: 3151992
Application: outdoor use only, embedded in concrete, asphalt, sand (see Step 1.1)
Minimum bend radius: 1 inch
Maximum exposure temperature (continuous and storage): 221°F (105°C)
Maximum exposure temperature (short-term for asphalt covering): 285°F (140°C)
Minimum installation temperature: 40°F (4.5°C)
Installation must be performed by qualified personnel, in accordance with local codes, ANSI/NFPA 70 (NEC
Article 426) and Section 62 of the CEC Part I.
Limited Warranty: For complete product warranty information, please refer to the web site. (see back of manual)