Fits ANY domestic and commercial refrigerator or room air conditioner from 1/8 H.P. to 5 H.P.
BC Series Bullet
®
Restricto Cap Tubing
Our Soft Copper Capillary Tubing is
precision plug drawn with the
internal diameter held to a tolerance
of +/- .001. It has been thoroughly
dehydrated, sealed and individually
packaged.
Features
Precision Bore, Plus or Minus .001
The Bullet Restricto Cap is consolidated into a
five-pak replacement kit. It's
guaranteed to provide you with uniformity on all
applications.
The five Restricto Cap sizes cover hundreds of
applications (see chart below).
Specification: ASTMB360
PART NO. SIZE LENGTH
BC1 .081 O.D. x .031 I.D. 10 FT. COIL
BC2 .093 O.D. x .040 I.D. 12 FT. COIL
BC3 .093 O.D. x .052 I.D. 12 FT. COIL
BC4 .125 O.D. x .064 I.D 12 FT. COIL
BC5 .071 O.D. x .028 I.D. 10 FT. COIL
BC1-100 .081 O.D. x .031 I.D. 100 FT. COIL
BC2-100 .093 O.D. x .040 I.D. 100 FT. COIL
BC3-100 .093 O.D. x .052 I.D. 100 FT. COIL
BC4-100 .125 O.D. x .064 I.D. 100 FT. COIL
BC5-100 .071 O.D. x .028 I.D. 100 FT. COIL
5PAK Five pack replacement kit.
Cap Tubing
CTC3 Cap Tube Computer
Calculate the flow rate of a defective cap tube and duplicate that flow rate with cap tubes
that have a different I.D.
Features/Benefits
Computes inside diameter, length, refrigerant, horsepower, application and flow rate
Shows temperature/pressure charts for 12 refrigerants
Compact, light weight & easy to use!
Converts Cap Tubing used with refrigerants R12, 134A, R22, and R502 only.
Added Notes
Use R12 conversion for R416A
Use R134 conversion for R401A, R401B, R406A, R500, R409A
Use R502 conversion for R402B, R403B, R404A, R407C,R408A
Reference chart for Bullet
®
RestrictoCapillary Tubing for All Refrigerants in Low,
Medium and High Applications
NOTE: This chart is average measurements for average conditions, and may have to be fine tuned
for exact replacement. These charts are for Fan Cooled units only. Add 10% to the length of the cap
tubing for Static Cooled Units.
NOTE: Application Temperatures are Saturated Suction Temperatures (SST).
SINGLE FEED
REF hp -10 LOW +20 MED +45 HIGH
R12/R416A 1/8 hp 110" # 5 84" # 5 48" # 5
1/6 hp 71" # 5 96" # 1 72" # 1
1/5 hp 54" # 1 36" # 1 24" # 1
1/4 hp 43" # 1 90" # 2 60" # 2
1/3 hp 93" # 2 72" # 2 36" # 2
1/2 hp 96" # 3 48" # 3 90" # 4
3/4 hp 60" # 3 92" # 4 72" # 4
1 hp 36" # 3 84" # 4 54" # 4
1-1/2 hp 84" # 4 60" # 4 43" # 4
2 hp 55" # 4 40" # 4 26" # 4
REF hp -10 LOW +20 MED +45 HIGH
R134A / R401A 1/8 hp 121" # 5 92" #5 53" # 5
R401B/R406A 1/6 hp 78" # 5 106" #1 79" # 1
R409A/R500 1/5 hp 59" # 1 39" #1 26" # 1
1/4 hp 47" # 1 99" #2 66" # 2
1/3 hp 102" # 2 79" #2 39" # 2
1/2 hp 105" # 3 52" # 3 99" # 4
3/4 hp 66" # 3 101" #4 79" # 4
1 hp 39" # 3 92" #4 59" # 4
1-1/2 hp 92" # 4 66" #4 47" # 4
2 hp 61" # 4 44" #4 29" # 4
NOTE: For Multiple Feeds with smaller HPs than those shown in the charts.
Divide HP by number of feeds, go to Single Feed Chart, select a cap tube for the calculated HP and use that selection for each feed.
Ex: 1 HP, LOW, R12 5 FEED USE: 1/5 HP, LOW, R12, SINGLE FEED CHART
RESULT: 5 Feeds, 54 BC1