INSTALLATION INSTRUCTIONS SDV35 Direct-Vent Gas Fireplaces P/N 700036M Rev. G 01/2011 This manual is one of a set of two supporting this product. Refer to P/N 725039M for Care and Operation Instructions. Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 700036CF. MODELS MILLIVOLT: SDV35-N Portland US INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. INstallateur : Laissez cette notice avec l'appareil.
TABLE OF CONTENTS PACKAGING Packaging..........................................Page 2 Introduction.......................................Page 2 General Information...........................Page 2 Requirements for the Commonwealth of Massachusetts..Page 4 New York City Approval...................... Page 4 Cold Climate Insulation......................Page 5 Manufactured Home Requirements...Page 5 Location.............................................Page 5 Vent Termination Clearances . ...........
WARNING Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
5.0" WC (1.24 kPa) 10.5" WC (2.61 kPa) Propane 11.0" WC (2.74 kPa) 13.0" WC (3.23 kPa) Table 2 Manifold Gas Supply Pressure (millivolt) Fuel # Low High Natural Gas (Lo) 2.2" WC (.55 kPa) (Hi) 3.5" WC (.87 kPa) Propane (Lo) 6.3" WC (1.57 kPa) (Hi) 10.0" WC (2.49 kPa) Table 3 Test gauge connections are provided on the front of the millivolt gas control valve, identified IN for the inlet and OUT for the manifold side. Propane tanks are at pressures that will cause damage to valve components.
VERTICAL VENT (Rear Vent Application) HORIZONTAL VENT (Rear Vent Application without a chase) RECESSED INSTALLATION TOP VENT TOP VENT APPLICATION APPLICATION AP TOP PL V IC EN AT T IO N APPLICATION TOP VENT NT VE ION AR AT RE LIC P AP For cold climate installations, seal all cracks around the appliance with noncombustible material and wherever cold air could enter the room.
Vent Termination Clearances These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. Vertical Vent Termination Clearances TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Horizontal Overhang Terminate multiple vent terminations according to the installation codes listed above.
Exterior HORIZONTAL Vent TERMINATION Clearance Requirements NOTE: Local Codes Or Regulations May Require Different Clearances. * See Item D in the Text Below. P N NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service. Inside Corner Detail Exterior Wall O *18” Horizontal Termination G V 6” N Q V V Ventilated Soffit A Inside Corner in U.S. � A == 9” 12” in Canada Detail D H 3 ft.
Minimum Clearances to Combustibles Hearth Extension A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements. See Figure 7.
WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury. AVERTISSEMENT Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
fireplace specifications ** Framing with Square Horizontal Terminaion SV4.5HT-2 **Framing With Square Horizontal Termination SV4.5HT-2 Framing Dimensions - Inches (millimeters) Model A B C D E SDV35 42-1/4 (1073) 37-1/2 (953) 23-3/4 (603) 42-1/4 (1073) 16" (406) Natural (NG) & Propane (LP) Gas * The Steady State Efficiency numbers based on maximum vent configuration. Model Diagrams, illustrations and photographs are not to scale – consult installation instructions.
b Fireplace Dimensions - Inches (millimeters) Model A B C D E F SDV35 42-1/4 (1073) 57-1/2 (1461) 40-5/8 (1032) 19-3/16 (487) 28-3/4 (730) 6-1/8 (156) F Inches (millimeters) 7 1/4 (184) C E NoteModel SDV35 • Venting requirements for rear vent applications in corner installations, the horizontal vent length “a” to “b,” must not exceed 28 inches (711). • Dimensions D and F occur when one 45 degree elbow is connected directly to the appliance collar.
Step 3. Install the Vent System General Information These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Vertical Termination Systems (Roof) See Figure 19 and Figures 29-33 on Pages 17 and 18 and their associated Vertical Vent Tables which illustrate the various vertical venting configurations that are possible for use with these appliances. Secure Vent™ pipe applications are shown in these Figures; Secure Flex™ pipe may also be used.
Vertical (Offset) Installation Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Figures and Tables on Pages 17 and 18 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2 " (876 mm) and 46 1/2" (1181 mm). Refer to the Vent Section Length Chart on Page 13 for an aid in selecting length combinations.
Outer Pipe Of Chimney 14" Min. Firestop Thimble Pitched Roof Outer Pipe Of Chimney Note: Trim Thimble/ Extension To Desired Length And Pitch At The Roof Line Thimble SV-FSTFE E. Support the vertical vent run sections -Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet using field provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members with nails or screws.
J. Install the storm collar - Install the storm collar, supplied with the flashing, over the vent/flashing joint. See Figure 27. Loosen the storm collar screw. Slide collar down until it meets the top of the flashing. Tighten the adjusting screw. Apply non-combustible caulking or mastic around the circumference of the joint to provide a water tight seal. C D Framing Dimensions for Roof Inches (millimeters) Pitch C D 0/12 10-1/2 in. (267 mm) 10-1/2 in. (267 mm) 6/12 10-1/2 in. (267 mm) 12 in.
VERTICAL VENT FIGURES/TABLES Notes: • Secure Vent™ (rigid vent pipe) is shown in the Figures; Secure Flex™ (flexible vent pipe) may also be used. • It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. • SV4.
VERTICAL VENT FIGURES/TABLES (CONTINUED) Table C H+H1 Maximum H Maximum H1 V Minimum feet (meter) feet (meter) feet (meter) 5 (1.524) 2 (0.610) 1 (0.305) 10 (3.048) 4 (1.219) 2 (0.610) 15 (4.572) 6 (1.829) 3 (0.914) 20 (6.096) 8 (2.438) 4 (1.219) V + V1 + H + H1 = 40 feet (12.2 m) Max H = 8 feet (2.438 meters) Max. H + H1 = 20 feet (6.096 meters) Max. u Ceiling Firestop / Spacer (SV4.5VF) vWall Firestop/ Spacer (SV4.5HF) V1 u Ceiling Firestop / Spacer (SV4.
Building Support Framing Support Brackets TYPICAL HORIZONTAL VENT INSTALLATION Horizontal / Inclined Run SV4.5 HT-2 Termination Shown SV4.5E90 Elbow Ceiling Vertical Rise SV4.5L6/12/24/36/48 Vent Sections u Firestop / Spacer Support Bracket Spacing Every 5 ft (1.52 m) u When Using Secure Flex, Use Firestop / Spacer SF4.5VF See Figure 24 on Page 15 for vertical vent section support. Figure 34 B.
J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B. Assemble the vent system to point where the terminus of the last section is located relative to the exterior surface to which the termination is to be attached as shown in Figure 36 and Table 8 on Page 21. If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section.
See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses. Venting Components Required for Various Exterior Wall Thicknesses, when using Square Termination Kit (SV4.5HT-2) Vent Components Required Under no circumstances, may separate sections of concentric flexible vent pipe be joined together. Exterior Wall Thickness - inches (mm) Termination Kit Only 6 to 9-1/4 (152 to 235) Termination Kit and 6 In. Vent Section (SV4.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED) Table H H+H1 Maximum H H1 �Wall Firestop/Spacer (SV4.5HF) feet (meter) feet (meter) feet (meter) 5 (1.524) 2 (0.610) 1 (0.305) 10 (3.048) 4 (1.219) 2 (0.610) 15 (4.572) 6 (1.829) 3 (0.914) 20 (6.096) 8 (2.438) 4 (1.219) V + H + H1 = 40 feet (12.2 m) Max H = 8 feet (2.438 meters) Max. H + H1 = 20 feet (6.096 meters) Max. �Ceiling Firestop/Spacer (SV4.5VF) �When using Secure Flex, use Firestop/Spacer SF4.5VF.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED) Table K �Wall Firestop/Spacer H + H1 + H2 Maximum (SV4.5HF) H1 H2 Square termination (SV4.5HT-2) shown. feet (meter) feet (meter) feet (meter) 5 (1.524) 2 (0.610) 1 (0.305) 10 (3.048) 4 (1.219) 2 (0.610) 15 (4.572) 6 (1.829) 3 (0.914) 20 (6.096) 8 (2.438) 4 (1.219) V + H + H1 + H2 = 40 feet (12.2 m) Max H = 8 feet (2.438 meters) Max. H + H1+ H2 = 20 feet (6.096 meters) Max. �Ceiling Firestop/Spacer (SV4.
Vertical or Horizontal Venting Using Secure Flex Kits and Components Secure Flex™ venting kits and components may be used in any venting application in place of rigid Secure Vent™ (SV4.5) direct-vent components. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Secure Flex kits may not be modified; also, under no circumstances may separate sections of flex pipe be joined together. APPLY ONLY MIL-PAC BLACK HIGH TEMPERATURE SEALANT (Cat. No.
Step 4. Field Wiring Note: The gas valve is set in place and pre-wired at the factory. CAUTION Ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box. See Figure 47. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition. (In Canada, the current CSA C22-1 Canadian Electrical Code).
Step 5. Connecting Gas Line Gas Flex Line Connector All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 48 illustrates two methods for connecting the gas supply. A Sediment Trap is recommended to prevent moisture and debris in gas line from damaging the valve. The flex-line method is acceptable in the U.S.A. where local codes permit, however, Canadian requirements vary depending on locality.
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD): WARNING Never use an open flame to check for leaks. Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solution). Note: Using a soapy water solution is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time. A.
Step 7. INSTALL VOLCANIC STONE, GLOWING EMBERS AND LOGS WARNING • DO NOT attempt to install the logs until the appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out. • The size and position of the log set was engineered to give the appliance a safe, reliable and attractive flame pattern.
MODEL SDV35 Log Placement Instructions A LOG SET Catalog Number H3367 * Item Description A Log, Rear B Log, Top Left C Log, Center D Log, Top Right C * Item "letters" above correspond to photos D B Install the Embers, Volcanic Stone and Logs in the order shown here (1 through 5) and per the instructions on Page 28.
Step 8. Installing the Glass Door WARNING • Do not attempt to substitute the materials used on these doors, or replace cracked or broken glass. • Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstalling the glass door frame. • The glass door(s) of this appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
Burner Air Shutter Adjustment Procedure Burner Flame Appearance Model SDV35 WARNINGS • Air shutter adjustment should only be performed by a qualified professional service technician. • Ensure front glass panel are in place and sealed during adjustment. CAUTIONS • Soot will be produced if the air shutter is closed too much. Any damage due to carboning resulting from improperly setting the air shutter is n ot covered under the warranty. • The air shutter door and nearby appliance surfaces are hot.
Step 11. ATTACHING SAFETY-IN-OPERATION WARNINGS It is the installer's responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing consumers of safe operation of this appliance.
Installation Accessories Item Cat. No. Model Description 1 H1968 SV4.5HT-2 Horizontal Square Termination With Firestop / spacer (H2246) & Adapter (74L61) 2 H2152 SV4.5CGV-1 1 Vertical Termination Cap 3 77L70 SV4.5L6 6 Inch (152 mm) Vent Section 3 77L71 SV4.5L12 12 Inch (305 mm) Vent Section 3 77L72 SV4.5L24 24 Inch (610 mm) Vent Section 3 77L73 SV4.5L36 36 Inch (914 mm) Vent Section 3 77L74 SV4.5L48 48 Inch (1219 mm) Vent Section 3 77L75 SV4.
Installation Accessories Item Cat. No. 18 H1969 SF4.5HT-2 Horizontal Square Termination (without flex) 18 77L87 SFKIT12S Flex Square Term. (with 12 inch [305 mm] * compressed flex) 18 77L88 SFKIT18S Flex Square Term. (with 18 inch [457 mm] * compressed flex) 18 77L89 SFKIT24S Flex Square Term. (with 24 inch [610 mm] * compressed flex) 18 77L90 SFKIT36S Flex Square Term. (with 36 inch [914 mm] * compressed flex) 18 77L91 SFKIT48S Flex Square Term.
Installation Accessories Item Cat. No.
Installation Instructions Gas Conversion Kits WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life.
Step 6. See Figure 60 and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit. Pilot for SIT Millivolt Gas Valve Use a 7/16" open end wrench and turn the pilot hex fitting counter-clockwise 1/4 turn. (See Figure 63). Note - The orifice strip tab may be randomly located on any side of the hex fitting. c.
NOTES 38
NOTES 39
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information. Printed in U.S.A. © 2005 Lennox Hearth Products P/N 700036M REV.