Specification

Sure-Lites
TD505049EN
2017 11-29
Catalog #
Type
Date
Project
Comments
Prepared by
The Sure-Lites CHX series is a UL924 code compliant and Chicago
approved LED Exit. It is available with AC only mode or self-powered
that will operate for a minimum of 90 minutes during a power outage.
The self-powered version features a long life nickel cadmium battery.
Key features include universal mounting, a rugged white steel housing
and frosted glass lens that is available with Exit, Stair or Area of Rescue
nomenclature and all arrow options.
SPECIFICATION FEATURES
Electronic
- Dual 120/277 VAC Input Voltage
- 3 Watt power consumption
AC Only
- Long life low maintenance low
energy consumption LEDs
Self Powered
- Sure-Lites EZ Key patented
external battery disconnect
feature – prevents unnecessary
battery drainage, saves on
installation time
- Solid-state Voltage Limited
Charger
- Brownout Circuit
- Low-Voltage Disconnect
- Test Switch / Power Indicator
Light
- Standard 24 hour recharge time
(max)
Housing Construction
- 20-gauge steel housing
- White finish
- Universal pattern knockouts on
rear for direct mounting to
junction box
- Steel canopy allows ceiling or
end mounting
- Red silk-screened lettering on
white translucent, heat
tempered, impact resistant
glass lens
- Other open face lenses available -
consult Eaton representative
- Lens installs from side of fixture
for more convenient, safe
maintenance
Code Compliance
- Damp Location Listed
(-20 to 40 C, -4 to 105 F)
- UL 924 Listed
- Life Safety NFPA 101
- NEC/OSHA
- City of Chicago Fire Code
- EPACT compliant
Warranty
- Exit: 5-Year
- Battery: 7-year prorated battery
warranty
CHX SERIES
DESCRIPTION
2 5/16"
[59mm]
9"
[229mm]
12 1/4"
[311mm]
9/16"
4 3/8"
6 5/8"
[111mm]
[14mm]
[168mm]
STEEL EXIT
AC ONLY
SELF POWERED
LED
CHICAGO EXIT LIGHTING
ENERGY DATA
Maximum power consumption
under all charge conditions:
LED Exits:
Input Power:
120V = 3W
277V = 3W
CATALOG LOGIC
SAMPLE NUMBER: CHX61
Series Battery Face Options Arrow Options Signage Options
CHX = Steel LED Exit 6 = AC only
7 = self powered
1 = single face ___ = no arrow
AR = arrow right
AL = arrow left
DA = double arrow
____ = no signage
- Stair = "Stair" instead of Exit
- Fire Escape = Fire Escape
- Area of rescue = Area of Rescue
- AORA w/logo = AORA with a logo
CHX = Steel LED Exit 6 = AC only
7 = self powered
2 = double face ____ = no arrow
ARL = arrow right/left
DA = double arrow
____ = no signage
- Stair = "Stair" instead of Exit
- Fire Escape = Fire Escape
- Area of rescue = Area of Rescue
- AORA w/logo = AORA with a logo