EV-12015, EV-12020, EV-20815, EV-20820, EV-23010 User Manual 120 and 208/230 Volt Models Software Version 1.0 © 2014 Electronic Systems Protection, Inc. / Technical Support: 1-800-645-9721 / espei.
User Manual ©2014 Electronic Systems Protection, Inc. / Technical Support: 1-800-645-9721 / espei.
User Manual I. PRODUCT OVERVIEW 3 1. MODELS ........................................................................................................................................... 3 2. KEY FEATURES ................................................................................................................................ 3 3. TECHNICAL SUPPORT ........................................................................................................................ 3 II.
User Manual I. PRODUCT OVERVIEW The enVision PCS is a state-of-the-art, microprocessor-controlled, power filter engineered with real-time data acquisition and storage. 1. Models: This manual applies to the following enVision models: Model Number Voltage (AC RMS) Current (AC Amps) EV-12015 120 15 EV-12020 120 20 EV-20815 120/230 Split Phase 15 EV-20820 120/230 Split Phase 20 EV-23010 230 Single Phase 10 Outlet 2.
User Manual II. INSTALLATION INSTRUCTIONS 1. Filter Installation: a. Turn off the machine you are connecting to the Filter, and unplug the machine’s power cord from wall outlet. Éteignez la machine que vous connectez au filtre et débranchez de la prise murale le cordon d'alimentation de la machine. Apague la máquina que intenta conectar al filtro y desconecte el cable de alimentación de la máquina del tomacorriente. b.
User Manual d. Connect Equipment i. Make sure that the total amperage of all equipment plugged into the Filter does not exceed the maximum branch circuit rating. Assurez-vous que l'intensité totale de tous les appareils reliés au filtre ne dépasse pas la tension maximale du circuit de dérivation. Asegúrese de que el amperaje total del equipo conectado al filtro no supere la clasificación máxima del circuito de derivación. ii.
User Manual e. Connect Filter to Outlet: Plug the Filter input power cord into a properly grounded and compatible branch circuit outlet. The plug is used as the disconnect device. Please Note: Do not plug the Filter into a re-locatable power tap. i.
User Manual III. HARDWARE 1. Filter a. LCD Event Monitor The LCD EVENT MONITOR displays useful information related to data collection, device status, and troubleshooting. i. Normal Operation 1.
User Manual Under Voltages (Off) Under Voltages (Record) Over Voltages (Record) Over Voltages (Off) Surges Overload Last Recorded Event Outlet State (OS) On / Off User Control (UC) Turn Outlets On / Off Memory All Clear (ALC) Disturbance History Clear (dhC) Power Usage Clear (PUC) Disturbance Count Clear (dcC) Energy Display Clear (EdC) ©2014 Electronic Systems Protection, Inc. / Technical Support: 1-800-645-9721 / espei.
User Manual ii. Wiring Fault When connected to an incorrectly wired branch circuit outlet, in addition to the illumination of the Red LED, the LCD Event Monitor will display the following information: iii.
User Manual b. Clearing Memory: The memory contents of the Filter can be cleared at any time by following one of these two methods: i. Buttons: Follow these steps to clear the device memory: 1. 2. Press the Menu button until “UC” (User Control) is displayed. Next, press the Scroll Button to select which memory record to erase: Memory All Clear (ALC) Disturbance History Clear (dhC) Power Usage Clear (PUC) Disturbance Count Clear (dcC) Energy Display Clear (EdC) 3.
User Manual a. Overview i. The Data Interface Cable consists of a USB connection on one end, and a RJ-11 connection on the opposite end. ii. The USB connection plugs into an available USB port on your PC. The RJ-11 connection plugs into the RJ11 “OUT” Jack (labeled “Data Port”) on the enVision Filter, which is the jack closest to the LCD and buttons. b. Instructions for Data Retrieval i. ii. iii. iv. v.
User Manual IV. Troubleshooting The Filter and Data Interface Cable contain no user-serviceable parts. Do not attempt product disassembly, as this will void the product warranty. Le filtre et le câble d'interface de données ne contiennent aucune pièce réparable par l'utilisateur. N'essayez pas de démonter le produit, car cela annulerait la garantie du produit. El filtro y el cable de la interfaz de datos no son piezas que un usuario pueda reparar.
User Manual V.
User Manual Parameter Surge Event Definition Specification Filter has been exposed to a transient voltage in one of the 3 possible modes (between Live and Neutral, between Live and Ground, between Neutral and Ground) with a peak amplitude of 500V* or higher and a frequency of 20 kHz or higher. *500V surge voltage amplitude applies to IEEE C62.41 Category B Impulse; surge voltage amplitudes necessary for detection of other surge types may vary.