User Manual Firmware Version v2.04.281 Table of Contents 1. Introduction 5 2. Initial Set Up 6 3. Installation 3.1 120 Volt Connections 3.2 Ethernet Connections 3.3 RS232 (Serial) Port Connection 3.4 Temperature Sensor 3.5 Contact Closure Input 3.6 Auxilary Relay Outputs 7 7 7 7 8 8 8 4. LED Indicators 8 5. Web Server 5.1 Login 5.2 Administration 5.2.1 Reset Factory Defaults 5.2.2 Backup/Restore 5.2.3 System Info 5.3 Device View 5.4 Global View 5.5 Setup 5.5.1 Device Setup 5.5.
User Manual Firmware Version v2.04.281 7. Email Notification 24 8 SNMP 24 9. SDxP Protocol 9.1 Overview 9.2 Hello Handshake 9.3 SDxP Packet 9.4 Types 9.5 Descriptors 9.6 Payloads 25 25 25 26 27 27 30 10. Device Management Utility 32 11. Syslog 33 12. Rear Panel Reset Button 33 13 34 Firmware Upgrade 13. Specifications © 2015 SurgeX/Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.
User Manual Firmware Version v2.04.281 1. Introduction The SurgeX® Axess Elite is a single rack-space, 120V, 15 (20) amp, AC power conditioner that can be controlled over a network or the internet, through a direct serial connection, or through a contact closure input. The simple web server structure allows basic control of the outlets and viewing of status information all from the home page.
User Manual Firmware Version v2.04.281 The thirteen front panel LEDs provide indications for eight AC outlet On/Off status (green), two Auxiliary Relay Latched/Unlatched status (green), surge protection status (green), Shutdown status (amber), and AC mains power (red). 1 2. 2 3 4 5 6 7 8 A B Self-Test Shutdown Mains Initial Set Up *Default user name and password: admin / admin DHCP *Beginning with firmware version 2.04.281, the factory default IP Mode will be DHCP (previously Static).
User Manual Firmware Version v2.04.281 Example: Telnet to DHCP-Assigned IP Address 192.168.1.199 on Port 23 and change to Static IP Address 192.168.1.3. Axess ELITE Connected to Telnet Session 1 User> admin Password> ***** Axess ELITE> set ipmode static OK Axess ELITE Reboot Required > set ipaddress 192.168.1.3 OK Axess ELITE Reboot Required> set subnet 255.255.255.0 OK Axess ELITE Reboot Required> set gateway 192.168.1.7 OK Axess ELITE Reboot Required> reboot 3.
User Manual Firmware Version v2.04.281 3.4 Temperature Sensor In order to obtain a temperature reading, the external temperature sensor must be connected to the first (far left) terminal block. The sensor has two wires: red and black. Connect the red wire to pin 1 and the black wire to pin 2.
User Manual Firmware Version v2.04.281 5. Web Server The web server is built around 4 pages: Login, Device View, Global View, and Setup. Each page is discussed in detail below. 5.1 Login The Login page is the first page displayed when a web browser makes a connection to the Axess Elite. Enter a valid user name and password in the “User Name” and “Password” fields, and press “Login” to log in to the Axess Elite. A mobile login page is available at IPAddress/mobile_login.html 5.2 Administration 5.2.
User Manual Firmware Version v2.04.281 5.3 Device View The Device View page provides information and status for the whole unit and individual outlets, as well as basic control of outlets. The top left section of the page provides system status. To refresh the status information, click the “Refresh” button. For each outlet the Outlet Name, Present State, Current Draw, Power Draw, and Energy Usage are displayed. Mobile Page links are at the bottom left below the Links section.
User Manual Firmware Version v2.04.281 5.4 Global View The Global View page displays the current outlet states and system status for the Axess Elite and expansion units. Up to 15 expansion units may be set up on the Links Setup page. Outlets and Aux Relays may be commanded to turn On, Off, or Reboot for up to 16 Axess Elite units (1 master and 15 expansions).
User Manual Firmware Version v2.04.281 5.5.1 Device Setup The Device Setup page allows for the specification of basic device parameters. Saving any change which requires a reboot to take effect will result in the addition of a “Reboot Required” button at the bottom of the page.
User Manual Firmware Version v2.04.281 5.5.2 Network Setup The Network Setup page allows for the specification of network settings, including the network adapter, email, and time keeping. Saving any change which requires a reboot to take effect will result in the addition of a “Reboot Required” button at the bottom of the page. © 2015 SurgeX/Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.
User Manual Firmware Version v2.04.281 Network Setup Item IP Setup IP Address Subnet Mask Gateway DNS1 DNS2 Web HTTP Port Web HTTPS Port SSL Required Enable Telnet Telnet Port Enable Email Email Server Login Name Login Password Return Address Auto Retry Test Email Set Time SNTP Server Time Zone Offset Use DST DST Start Date DST Stop Date Manual Time Set Description Specifies whether to use Static or DHCP mode.
User Manual Firmware Version v2.04.281 5.5.3 Network Reporting Setup The Network Reporting Setup page allows for the configuration of SNMP, SDxP, and Syslog reporting. Saving any change which requires a reboot to take effect will result in the addition of a “Reboot Required” button at the bottom of the page. Network Reporting Setup Item Description Enable SNMP Specifies whether or not to enable the SNMP v2c agent. Read Community Specifies the read community string.
User Manual Firmware Version v2.04.281 5.5.4 Users Setup The Users Setup page allows for the creation, deletion, and editing of up to 8 user accounts. Each user will have a unique user name, password, and email address, and may be assigned access to specific outlet(s). User accounts may be of the Administrator or User type. Administrators have access to all functions; Users do not have access to Setup functions. User authentication is supported for Web, Serial, Telnet, and SDxP interfaces.
User Manual Firmware Version v2.04.281 5.5.5 Triggers Setup The Triggers Setup page allows for the modification of System Triggers and creation of User Triggers. System Triggers define the protective shutdown points for the AC outlets, and take precedence over all other actions, including User Triggers.
User Manual Firmware Version v2.04.281 5.5.6 User Defined Triggers User defined triggers that have previously been created are displayed in a list. The name of the trigger is the name that was given to the trigger when it was created. Pressing “Test Alarm” will activate the trigger alarm action, and pressing “Test Clear” will activate the trigger clear action; use these test functions to verify that the trigger will operate as intended.
User Manual Firmware Version v2.04.281 5.5.7 Sequences Setup The Sequences Setup page allows for the creation and modification of sequences. A sequence is a list of outlets, including Auxiliary Relays, that will be turned On, Off, or Rebooted in a predetermined way with a specified delay time between each step. Using sequences avoids manually turning each outlet on or off individually. A sequence, as defined for this product, is purely a one-way sequence.
User Manual Firmware Version v2.04.281 5.5.8 Links Setup The Links Setup page allows for the setup of Axess Elite Expansion units and Favorites. Expansion units are other Axess Elite units which will be available for monitoring and control on the Global View page of the master unit. Up to 15 Expansion units may be defined. Favorites may be any internet address. Use Favorites to set up shortcuts to earlier versions of the Axess Elite product, other equipment web servers, or Internet web pages.
User Manual Firmware Version v2.04.281 6. Command Line Interface (CLI) Protocol The Command Line Interface provides complete setup of all functions of the Axess Elite. The CLI may be accessed either via the network interface using Telnet, or via the serial port using a terminal emulator program. Some commands of the CLI require administrative rights; these are indicated in the following tables. 6.1 Prompts 6.
User Manual Firmware Version v2.04.281 6.5 Device Commands Command get outlet <1‐10> set outlet <1‐10> get devicename set devicename get reboot set reboot <1-99> get delay set delay <0-99> get console set autologout <0-99> set baud < 2400 | 9600 | 57600 | 115200 > clear shutdown set clear shutdown by user < yes | no > get upload enable set upload enable < yes | no > clear log set factory defaults logout reboot Description Admi Returns the status of the specified outlet.
User Manual Firmware Version v2.04.281 6.6 6.7 Network Commands Command get network get mac set ipmode < static | dhcp > set ipaddress < dotted decimal > set subnet < dotted decimal > Description Returns the network settings. Returns the MAC address of the network adapter. Sets the IP Mode. Sets the IP Address in dotted decimal. Sets the subnet mask in dotted decimal.
User Manual Firmware Version v2.04.281 7. Email Notification Email can be automatically sent for System Triggers and User Triggers. Emails generated by the Axess Elite will display the device name and information related to the System Trigger or User Trigger. Examples: Subject : Axess ELITE Cabinet_1 Date : Sat, 7 Jul 2012 09:41:00 - 0500 From : To : networkadmin@yourco.com Axess ELITE Cabinet_1 at 192.168.1.
User Manual Firmware Version v2.04.281 9. SDxP Protocol 9.1 Overview The SDxP Protocol is a packet-based protocol designed to be extensible. This protocol is transmitted over TCP on a user-defined port. The factory default SDxP port is 9100. The protocol uses a Hello handshake to establish unique sequence numbers to allow for advanced security when AES encryption is used. With AES enabled, all messages must be encrypted with the AES Passphrase set in the device.
User Manual Firmware Version v2.04.281 9.3 SDxP Packet The packet is broken up into 2 parts: the Header and the Payload Header The header is used to carry general information, such as is shown in the C programming structure below: typedef struct { eType type; char[21] uName; char[21] password; uChar desc; uChar param; uint16 seq; } THeader Variable type uName password desc param seq Description Enumerated type that tells the SDxP server what type of packet is being sent.
User Manual Firmware Version v2.04.281 9.4 Types There are currently 2 types. All classes are defined in the C programming enumerated type definition below: typedef enum { eType_null, eType_inform, eType_commands } eCmnd; 9.5 0 1 Command eType_null eType_inform 2 eType_commands Description This is a null command and should not be sent to the server. Informs are similar to SNMP traps. They are sent from the managed device to the manager on a periodic basis.
User Manual Firmware Version v2.04.
User Manual Firmware Version v2.04.281 eType_Commands Commands are used to control and query the managed device.
User Manual Firmware Version v2.04.281 9.
User Manual Firmware Version v2.04.
User Manual Firmware Version v2.04.281 tAuxCommand 10.
User Manual Firmware Version v2.04.281 11. Exit: Exits the DMU program Help: Online Help: Opens a web browser to online help resources About: Displays DMU version information Syslog The Axess Elite contains a built in Syslog client. When enabled, it will send Syslog formatted UDP messages on port 514.