Batter Runtimes
Battery UPS-BPX-1000
Compatible UPS UPS-1000-OL
Capacity Watts Internal INT+1 EXT INT+2 EXT INT+3 EXT INT+4 EXT
0 0 203 893 >16 hrs >16 hrs >16 hrs
10 80 48 211 419 659 925
20 160 24 107 212 334 468
30 240 15 68 135 213 298
40 320 11 49 97 152 213
50 400 8.4 37 74 116 163
60 48 6.7 30 59 93 130
70 560 5.6 24 49 77 107
80 640 4.7 20 41 64 90
90 720 4.1 17 35 55 78
100 800 3.5 15 31 48 68
Runtimes are expressed in minutes.
Typical runtimes based on fully charged, new batteries, operating under typical load conditions.
Times estimated assuming a switch mode power supply.
Runtimes are affected by battery age, ambient temperature, site specific usage patterns and load conditions.
Percent
Number of Battery Packs
Battery UPS-BPX-2000
Compatible UPS UPS-2000-OL
Capacity Watts Internal INT+1 EXT INT+2 EXT INT+3 EXT INT+4 EXT
0 0 517 >16 hrs >16 hrs >16 hrs >16 hrs
10 160 60 267 532 836 >16 hrs
20 320 27 121 242 380 533
30 480 16 74 147 232 325
40 640 11 52 103 162 227
50 800 8.9 39 77 122 171
60 960 7.0 31 61 96 135
70 1120 5.7 25 50 79 111
80 1280 4.8 21 42 66 93
90 1440 4.1 18 36 57 80
100 1600 3.6 16 31 49 69
Percent
Number of Battery Packs
Battery UPS-BPX-3000
Compatible UPS UPS-3000-OL
Capacity Watts Internal INT+1 EXT INT+2 EXT INT+3 EXT INT+4 EXT
0 0 351 >16 hrs >16 hrs >16 hrs >16 hrs
10 240 56 247 491 772 >16 hrs
20 480 26 117 232 365 512
30 720 16 72 144 226 318
40 960 11 51 101 159 223
50 1200 8.8 38 77 120 169
60 1440 7.0 31 61 96 134
70 1680 5.7 25 50 78 110
80 1920 4.8 21 42 66 93
90 2160 4.1 18 36 57 80
100 2400 3.6 16 31 49 69
Percent
Number of Battery Packs
UPS Battery Runtimes
© 2016 AMETEK Electronic Systems Protection. All rights reserved.