CYCLE LIFE
Battery manufacturers rate the cycle life of their batteries by comparing the level 
of discharge on the battery and the frequency of cycling. Higher battery discharge 
will result in shorter cycle life. In reverse, a smaller discharge percentage will 
extend the expected cycle life of the battery as the battery will provide more 
charge/discharges. To provide an example of cycle life, a 48V string of 8 x 6 
volt S-550 models in series (428 AH capacity @ C20 ) which are consistently 
discharged to 50% state of charge (214 AH of capacity drawn) and consistently 
recharged to a full state of charge should provide approximately 1280 cycles 
before end of life.
With traditional off-grid Renewable Energy systems, DOD is set to operate 
between 20% and 50% to maximize the life of the batteries. Battery-based 
systems are designed to allow a maximum 50% DOD as this offers a balance 
between capacity vs. cycle life, also taking into consideration the cost  
of replacement.
For grid-connected backup systems, Installers will typically design battery 
banks to operate to a greater DOD percentage to lower initial installation costs. 
Cycling with grid-connected systems is significantly less frequent than with 
off-grid, where this may occur daily, a lower DOD is acceptable as long as the 
customer understands that the overall cycle life is affected when they cycle 
their battery bank beyond a 50% state of charge.