Operation Manual

9. Sensor signal outputs
9.3 Modbus output
Mode : RTU
Baud rate : 19200
Device address : 1
Framing / parity / stop bit : 8, N, 1
Response time : 1 second
Response delay : 0 ms
Inter-frame spacing : 7 char
Remarks
You can change Modbus communication settings using the S4C-FS
Service App and the optional local display. For instructions, see the next
two chapters.
Index Channel description Resolution Format Length
Modbus
address
1 Flow 0.1 FLOAT 4-Byte 6
2 Consumption 1 UNIT32 4-Byte 8
3 Temperature 0.1 FLOAT 4-Byte 0
4
Reverse flow
0.1 FLOAT 4-Byte 12
Remark
All numbers are in the little-endian format.
Function code: 03.
Different units have different precisions.
The measurement values are always available in the programmed
physical units.
24 S 421