6 Technical data
6.3 Output-signals
Analogue output Signal: 4 ... 20 mA, isolated
Scaling: 0 to max flow
Max load: 250R
Pulse output 1 pulse per consumption unit, isolated switch,
max. 30 VDC, 200 mA (pulse length: 10 ... 120
ms, depending on flow rate)
Modbus output See chapter 10.3
6.4 Accuracy
Accuracy* ±(2% of reading + 0.3% FS)
Temperature drift: < 0.05%/K
Stated accuracy at Ambient/process temperature 23°C ± 3°C
Ambient/process humidity <90%
Process pressure at 0.6 MPa
Repeatability ±0.25% of reading
*Specified accuracy is valid only within the minimum and maximum flow
rates that are indicated in section 6.5.
10 S402