Step
Description
Illustration
5.
Reassemble the bottom lid and make sure to
tighten the glad so that is seals around the
temperature probe wire.
If the wire is too thin use an additional crimp
sleeve around the wire before entering it into
the gland
6.
The Temperature probe tip should be
squeezed between the (U)HT Deployment kit
or band and the pipe. Make sure that this
does not interfere with the alignment of the
Deployment kit. Bend the sheathed part of the
temperature sensor so that it runs in parallel
with the (U)HT senor sheathed cable and into
the conduit.
6.4.5 Start-up
Before powering the PipeMonit Swarm S2 check that all
cables are properly connected. Verify that Intrinsically Safe
cables, conduits, and cable trays are segregated (no direct
contacts with other non I.S. conductors).
Start-up is done by connecting the power socket from the
battery pack to the top board, please note that this needs to
be done while the Swarm S2 Datalogger top lid is open. This
can be done without a hot work permit since the product is
intrinsically safe.
Open the top lid using a hex key and pull the top lid straight
up until the connector let go, then flop then lid over as
illustrated. The lid will hang safely in the rubber hinge, and
the bolts are secured with retaining washers so that do not
fall out during this operation. See also Section 8.4
Regardless of this, use caution when connecting the battery.
Figure 10 Battery connection