Installation Instructions

Installation et connections Page 23/57
Installation and starting instructions
d) Digital inputs DI1 to DI5
Controller has 5 digital inputs on which a tank bottom, flow, R.I.C (Remote Input Control), or another
sensor can be connected.
The definition of supported sensors is as follows:
0…20l/min
0…50l/min
0…200l/min
0…10m3/H
Customer*
Flow (impulsions)
(*): The scale of the customer can be defined between 0 et 2000
(L/min, L/H or m3/H) in 4…20mA or impulse input
Connection of a R.I.C (Remote Input Control), tank bottom or another sensor on DI1:
Preferably use a two-strand cable.
Connect one sensor strand to the DI1 sw (17) connection.
Connect the other sensor strand to the DI1 - (18) connection.
Tighten the cable gland to seal.
Connection of a flow switch sensor on DI2:
Remove the protective sheath.
Strip the wires on 7mm.
Pass the cable through the cable gland.
Connect the brown power strand to DI2 + (29).
Connect the blue power strand to DI2 – (31).
Connect the black contact strand to DI2 sw (30).
Tighten the cable gland to seal