Programming Instructions

SYCLOPE COOLTOUCH setting Page 14/40
Communication programming instructions
a) Modbus Configuration [1731]
Press to open following screen.
Modbus sur RS485
Mode RTU
- Selection of the Modbus communication mode, on this selection button we find the information of the
selected mode (RTU) Press to change it.
Speed 19200
- Selection of the Modbus communication speed, on this selection button we find the information of the
selected speed (19200). Press to change it.
Parity None
- Selection of the Modbus communication parity, on this selection button we find the information of the
selected parity (None). Press to change it.
Stop bit(s) 2
- Information on the configuration of the number of stop bit(s). This option is not configurable, it adapts
according to the parity configuration and here is just information to help you configure your connection.
Address 1
- Modbus address input of your regulator. Here the current value is (1).
Press it to open the numeric keypad and enter the desired value.
Possible adjustment from 1 to 247.
MODBUS
Modbus settings
Mode RTU
Modbus over RS485
Speed 19200
Modbus TCP
Stop bit(s) 2
Address
1
Parity None
Peripheral WIFI
Port 502
Simultaneous connection(s) 1
Pseudo address 255