Programming Instructions

Programming screen « Setup menu » Page 35/78
General programming instructions
Tank low level detection Switch level DI2
- Selection of the tank low level detection to which this relay is attached, on this selection button we
find the information of type of parameter (Switch level) and its “code” (DI2). Press to change it.
Pump flow rate 0 l/h
- Enter the value of the pump flow rate. The value will be used in the calculation of the remaining level
in the tank. Here the value is (0).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0.01 to 1000.00 l/h
Tank volume 0 l
- Enter the value of the tank volume. The value will be used in the calculation of the remaining level in
the tank. Here the value is (0).
Press to open the numeric keyboard and enter the desired value.
Possible adjustment from 0 to 65000 l
Compute enables
The “Pump flow rate” and “Tank volume” windows are greyed out. You must check the “Enable
compute” box to make them active and to active the calculation of the remaining volume in the tank of
Biocide A.
c) CRT Relay outputs FO3 & FO4 [2531]
Special “Inhibitor” or “Dispersant” case
FO3 Function Inhibitor
- Output CRT relay operation mode selection, on this selection button we find the information of the
output being modified (FO3) and the function currently selected (Inhibitor). Press to change it.
Operation Continuous
- Operating mode selection, on this selection button we find the selected operating mode information
(Continuous). Press to change it
Tank low level detection, Pump flow rate, Tank volume, Enable compute
- See previous paragraph.
Relay settings
FO3 - Function Inhibitor
Operating mode Continuous
Tank low level detection
None
Tank volume
Enable compute
l/h l 0 0
Pump flow rate