Programming Instructions

Programming screen « Setup menu » Page 49/78
General programming instructions
c) Inhibitor - Dispersant:
Injection
- There are 3 possibilities that depend on the setting of the output.
Continuous
Injection every minute
Inhibitor or dispersant is dosed at
periodic intervals. During the purge
period, operation is suspended. Press to
toggle the mode from minute to hour.
For 20 s
Enter the desired inhibitor or
dispersant time value. Press to open the
numeric keyboard and enter the desired
value.
Possible adjustment in “Minute”
mode from 0 to 59 s and in “Hour”
mode from 0 to 3600 s
Percent
Injection in percent of bleed
time 20 %
Inhibitor or dispersant are dosed
after desalination in proportion to the
opening time of the valve.
Determination of the % ratio
between the time of desalination and the
time of dosing inhibitor or dispersant.
Press to open the numeric keyboard and
enter the desired value.
Possible adjustment from 0 to 100
%
Volumetric
Injection every 10 l
Inhibitor or dispersant are dosed
after counting a predefined volume.
Press to open the numeric keyboard
and enter the desired value.
Possible adjustment from 0 to
10000 l.
For 40 s
At the end of the predefined
counting, inhibitor or dispersant are
dosed for a programmed time.
Enter the desired injection time
value. Press to open the numeric
keyboard and enter the desired value.
Possible from 0 to 3600 s
Inhibitor (Continuous)
Injection every
minute
20
For
s
Inhibitor (Percent)
Injection in percent of bleed time
20
For
%
Inhibitor (Volumetric)
Injection every
10
40
For
s