Programming Instructions

Programming screen « Setup menu » Page 51/78
General programming instructions
d) Measure Alarm
E04 Free chlorine AI1
- Parameter identification, includes information on parameter number (E04), type (Free chlorine) and
associated main sensor input (AI1)
Low alarm Enable
- You must check this option to enable low alarm threshold management. Here the management is
unchecked.
Threshold 1.00 mg/l
- Enter the low alarm threshold value. Here the current value is (1.00).
Press to open the numeric keyboard and enter the desired value.
High alarm Enabled
- You must check this option to enable high alarm threshold management. Here the management is
checked.
Threshold 9.00 mg/l
- Enter the high alarm threshold value. Here the current value is (9.00).
Press to open the numeric keyboard and enter the desired value.
ALARM THRESHOLD SETTINGS
E04 Free chlorine AI1
Low alarm Enable
Threshold 1.00
mg/l
High alarm Enabled
Threshold 9.00
mg/l
Hysteresis 0.50
Time limit OFF
mg/l
s
Stop dosing on alarm
High
threshold
Time
Measure
Time
Alarm
Low
threshold
Hysteresis
Hysteresis
Time