General programming instructions
e) Measure Setpoint
When the dosing direction of the channel is configured in downstream mode, as soon as the error
(measurement – setpoint) is greater than the hysteresis value, the regulation requirement is 100%.
When the dosing direction of the channel is configured in upstream mode, as soon as the error (setpoint
– measurement) is greater than the hysteresis value, the regulation requirement is 100%.
E04 Conductivity AI1
- Parameter identification, includes information on parameter number (E04), type (Conductivity) and
associated main sensor input (AI1)
Mode Hysteresis
- Dosage mode selection, on this selection button we find the selected mode information (Hysteresis).
Press to modify it.
Setpoint 2.00 mg/L
- Enter the setpoint value. Here the value is (2.00).
Press to open the numeric keyboard and enter the desired value.
Hysteresis 0.10 mg/L
- Enter the hysteresis value. Here the value is (0.10).
Press to open the numeric keyboard and enter the desired value.