Programming Instructions

Programming screen « SETTINGS » Page 56/78
General programming instructions
7) Menu « Settings » - « Outputs 4…20mA » [0721]
« TRANFERTS 4…20mA » menu will allow you to adjust the threshold settings of the parameters.
Press to open following screen
4…20mA transfer threshold with possible setting.
Press to open calibration screen
4…20mA transfer threshold not configurated.
A01 Conductivity E04
- Parameter identification, we find the parameter number identification (A01); type (Conductivity)
and associated sensor input (E04).
Transfer value for 4mA 0 mS/cm
- Enter the corresponding pH value for 4mA at transfer output. Here the value is (0).
Press to open the numeric keyboard and enter the desired value.
Transfer value for 20mA 20.00 mS/cm
- Enter the corresponding pH value for 20mA at transfer output. Here the value is (20.00).
Press to open the numeric keyboard and enter the desired value.
Save:
- When a change is made, the “SAVE” button appears (floppy icon), you must save your configuration
by pressing it.
Outputs
4…20mA
4 20mA OUTPUT SETTINGS
AO1 Conductivity E04
AO1 Not used
Transfer value for 4mA
Transfer value for 20mA
0
20.0
mS/cm
mS/cm
Transfer value for 4mA
Transfer value for 20mA
Transfer value for 4mA
Transfer value for 4mA
0
mg/l