Installation Instructions

Installation and connections Page 19/67
Installation and starting instructions
Reconnect the flat cable between the cards and reassemble the front panel using the 4
fixing screws. Don’t overtighten because the screws are fixed in the plastic case.
Reconnect the flat cable and replace the front panel before switch On.
8) Primary power connections
SYCLOPE ODITouch
®
has a switch-mode power supply. It can be powered by an alternating
voltage between 100V and 240V 50/60Hz.
Use a 3-point 1.5 mm
2
to wire the power supply
Strip the 3 wires on 7mm
Pass the 3-point cable through a cable gland
Connect the phase on L1 and the neutral on the N of the main terminal block X1
Connect the earth on the PL1 stud using an M4 eyelet terminal
Tighten the cable gland to seal.
Your SYCLOPE ODITouch
®
doesn’t have a power switch. So it’s directly supplied when it’s
connected to the mains.
Your SYCLOPE ODITouch
®
doesn’t have a power switch. It is therefore necessary to install
a 10A circuit breaker upstream of the device.
Locate the fuse to be changed
on the lower PCB
Fuse F1 (TR5)
Fuse F2 (TR5)
Remove the fuse to be changed
Replace the new fuse