9. CONNECTION TERMINALS
WIEGAND
HARNESS
BACK-LIT JUMPER
K OR A JUMPER
OUTPUT 2
JUMPER
CONNECTION
TERMINALS
1 - 2: 12-24V DC (Power Input Terminal)
Connect to 12-24V DC power supply. The (-) supply and the (-) GND are the common grounding points of the system.
The system accepts full input voltage range with no adjustment.
3 - 4 - 5: OUTPUT 1 (Output Relay 1)
5 Amp relay dry contact controlled by the Group 1 User Codes/Cards, recommended for door strike. Terminal 3 is
Normally Closed (N.C.), terminal 5 is Normally Open (N.O.) and terminal 4 is the common point of the two contacts.
Use N.C. output for Fail-safe locking device; and N.O. output for Fail-secure locking device. The relay is programmable
for Start/Stop (toggle) mode or Momentary timing mode. See programming Location 51 for the details.
6 – 7: OUTPUT 2 (Output Relay 2)
1 Amp relay dry contact controlled by the Group 2 User Codes/Cards. It is an auxiliary output contact for controlling
security system or automatic operator. It is selectable for N.C. (Normally Closed) or N.O. (Normally Open) with jumper
and the operation mode is programmable for Start/Stop (toggle) or Momentary with timing. See programming Location
52 for the details.