Instructions
33
19. OUTPUT MODE & TIMING FOR OUTPUT 1, 2 AND 3
-- Locations 51, 52 & 53
The three relay outputs are programmable for Start/Stop or Timing modes. Apart from door access control, alarm
arm-disarm control, they are also universal timers for automatic operators in industry with their 99,999 seconds
(over 24 hours) programmable timer.
LOCATIONS
→
OUTPUT MODE & TIME
→
VALIDATION
51 - 53 0 or 1 - 99999 #
(1) (2) (3)
(1) LOCATIONS
51 -- Location for Output 1
52 -- Location for Output 2
53 -- Location for Output 3
(2) OUTPUT MODE & TIMING
0 - Start /Stop Mode (Toggle)
The number 0 sets the output to Start / Stop mode. The output Starts when an User Code and/or Card is entered/
read; the output Stops when an User Code and/or Card is entered/read again.
1 - 99999 -- Seconds Momentary --- (Default -- Momentary 5 Seconds)
The output can be set in Momentary Mode with the time of 1 second to 99,999 seconds. The output will reset
automatically when the time expires.
(3) VALIDATION
Press # key once. Two-beep conrms the entry.
RESET OUTPUT TIMER WITH SUPER USER CODE
The Output Timer can be RESET manually at anytime with the Super User Code that operates the desired output
before the end of the time.
Example:
Reset Output 1 Timer --
SUPER USER CODE
#1 ------------- Output 1 stops
Reset Output 2 Timer --
SUPER USER CODE
#2 ------------- Output 2 stops
Reset Output 3 Timer --
SUPER USER CODE
#3 ------------- Output 3 stops