Instructions
69
b) DOOR SENS
MAGNETIC
DOOR
SWITCH
With the help of a Normally Closed door position sensor
(usually a magnetic door switch) on the door to set up the
following functions:
• Door Auto Relock -- The system will immediately relock
the door after a valid access has been gained to prevent
“tailgate” entries.
• Door Forced-open Alarm -- The keypad will generate
alarm instantly if the door is forced to open. Enable the
function at Location 80.
• Door Propped-up Alarm -- The keypad will generate
alarm if the door is left open longer than the pre-set
delay time. Enable the function at Location 81.
• Inter-lock Control -- When the door is open,the
interlock output of the keypad will give a (-) command to
stop the other keypad in an inter-lock system.
• Door Opening Alarm -- Door Opening Alarm is
designed for the emergency door only. It is always given
when the door is opened unless a valid user code or
card is used prior to the door is opened. Enable the
function at Location 91.
c) ALARM OUTPUT -- SET THE “K OR A” JUMPER TO “A”
ALARM CONTROL PANEL
LOW POWER
PIEZO BUZZER
24 HOUR N.O.
PROTECTION
ZONE
LED
OR
The Alarm Output switches to (-) ground in door forced to open or the door open after Egress Delay. You may use it
to turn ON an LED lamp and/ or a small buzzer to notify a guard; or connect it to a 24 hour Normally Open protection
zone of an alarm system. See Location 80 and Location 91 for more information about these functions.
• Only one connection option is recommended. Make sure that the sink current does not exceed the maximum rating
of 100mA.