Instructions

17
Jumper Setting for Link-up Procedures
It is necessary to send the Master Code (the link-up code) of the keypad to the decoder for it to recognize the keypad
working with it. The decoder will refuse other keypad that is not registered. The keypad will generate warning beep
continuous once per second if link-up is unsuccessful.
Link-up Procedures:
Put the “Link-up Jumper” from OFF to ON position (the jumper is located on the main circuit board next to the
connection terminals).
OFF
ON
Set the keypad to programming mode with Master Code
MASTER CODE
* *
---- 2 beeps from keypad
Set the keypad to exit programming mode and the Link-up Code will be sent to the decoder automatically
* *
---- 2 beeps from keypad
Put the “Link-up Jumper” back to OFF position to lock the code in decoder after link-up
ON
OFF
Always keep “Link-up Jumper” on OFF position in normal operation
Split-decoded keypad requires link-up Only Once unless the master code is changed. The link-up code
in the decoder (same as the master code in keypad) is protected. It is not affected due to the keypad in
programming mode. However, the system requires link-up again if the Master Code of the keypad has been
changed.
ALARM OUTPUT & WARNING
1) Tamper ALarm:
The alarm is triggered via the “Tamper In” terminal
Alarm Output and Internal Siren activate
The alarm period is xed in 3 minutes
It can be reset with
SUPER USER CODE
# 1 or an user Code/Card in Group 1
Alarm & Warning in Split-decoded Operation
2) The Egress Delay Alarm
The Egress Delay Alarm is enabled by programming from keypad at Programming Location 90
The alarm activates during the egress Delay period
Alarm Output and Internal Siren activate
3) Egress Delay Warning:
The Egress Delay Warning is enabled by programming from keypad at Programming Location 90
The warning activates during the Egress Delay period
The warning beep is given by the internal buzzer only