Operation: Taking Duress Code 3 3 6 9 in Group 1 for Output 1 As Example
READ CARD
3369 #
(a) (b) (c)
a) Read the EM card. Two-beep conrms the reading and 30 seconds waiting time is given for the entry of Duress
Code, the Amber LED keeps ashing
b) Key in the Duress Codes 3 3 6 9 for operating Output 1
c) Conrm it with the # key. Output 1 activates in a normal way and the Duress Output also activates to report Duress
Event to an alarm system if connected.
Duress Event can not be reported with EM Card alone. User can only directly use Duress Code to open the
door and report duress event in emergency
19. OUTPUT MODE & TIMING FOR OUTPUT 1, 2 & 3 --
Locations 51, 52 & 53
The three relay outputs are programmable for Start/Stop or Timing modes. Apart from door access control, alarm
arm-disarm control, they are also universal timers for automatic operators in industry with their 99,999 seconds
(over 24 hours) programmable timer.
LOCATIONS
OUTPUT MODE & TIME
VALIDATION
51 - 53 0 or 1 - 99999 #
(1) (2) (3)
(1) LOCATIONS
51 -- Location for Output 1
52 -- Location for Output 2
53 -- Location for Output 3
(2) OUTPUT MODE & TIMING
0 - Start /Stop Mode (Toggle)
The number 0 sets the output to Start / Stop mode. The output Starts when an User Code and/or Card is
entered/read; the output Stops when an User Code and/or Card is entered/read again.
1 - 99999 -- Seconds Momentary --- (Default -- Momentary 5 Seconds)
The output can be set in Momentary Mode with the time of 1 second to 99,999 seconds. The
output will reset automatically when the time expires.
(3) VALIDATION
Press # key once. Two-beep conrms the entry.