28. DOOR PROPPED-UP WARNING & THE DELAY TIME
-- Location 81
LOCATION
FUNCTION MODES
VALIDATION
81 0 or 1 - 999 #
(1) (2) (3)
(1) LOCATION
Key in Location 81
(2) FUNCTION MODES FOR DOOR PROPPED-UP WARNING
If somebody opened the door and left it open longer than the allowable delay time, the keypad will generate door
propped-up warning until the door is re-closed. There is warning beeps from the keypad only but it does not activate
the alarm output. This function works with a door position sensing switch equipped on the door.
0 --- Door Propped-up Warning OFF – (Default)
1 - 999 --- Door Propped-up Warning ON & The Delay Time
The Delay Time can be 1 to 999 seconds. It is the allowed time for door open without starting warning.
(3) VALIDATION
Press # key once. Two-beep conrms the entry
INTELLIGENT EGRESS BUTTON – AN UNIQUE FEATURE OF THE KEYPAD
INTRODUCTION
Most of the keypads for access control are just for controlling “Going In” from outside. It is not enough for today’s
access control systems. In fact, controlling “Going Out” is also very important in some public passage areas those
are not allowed to use locks or digital keypads for stopping of “Going Out” due to safety reasons. Such as hospitals,
kindergartens, elderly homes, convenient stores, emergency exits etc.. The wardens, teachers, shopkeepers and the
guards are always required to keep an eye on people to prevent unattended leaving, shoplifting, and unauthorized
use of the emergency exits.
The Intelligent Egress Button can be programmed to do something to get attention from the person on duty before
the door is opened. The button offers programmable egress delay, delay with warning, holding button for the delay,
momentary button contact with warning for the delay and even gives alarm when a controlled door is opened.
Locations 90 and 91 are the places for setting the desired functions for the Egress Button.
The functions programmed to the Egress Button do not affect the normal operation of the keypad. The operation of
the keypad with Code or Card is always in the rst priority to give instant action to the output relay 1 for door strike.
It is NOT required to program the Egress Button with the special function in normal use. Just leave it on its default
values.