(C) ALARM OUTPUT
ALARM
O/P
KEY ACT
O/P
GND
(
-
)
(
)
-
P
ALARM
O/
KEY ACT
O/P
GND
LOW POWER
PIEZO BUZZER
LED
ALARM CONTROL PANEL
OR
24 HOUR N.O.
PROTECTION
ZONE
The Alarm Output switches to (-) ground in door forced to open or the door open after Egress Delay. You may use it
to turn ON an LED lamp and/ or a small buzzer to notify a guard; or connect it to a 24 hour Normally Open protection
zone of an alarm system. See Location 80 and Location 91 for more information about these functions.
Only one connection option is recommended. Make sure that the sink current does not exceed the maximum rating
of 100mA.
(D) KEY ACTIVE -- OUTPUT
(
)
-
P
ALARM
O/
KEY ACT
O/P
GND
(
)
-
P
ALARM
O/
KEY ACT
O/P
GND
LOW POWER
PIEZO BUZZER
N.O. RELAY
CONTACT
ISOLATION RELAY
LED
OR
The Key Active Output switches to (-) ground for 10 seconds whenever a key is touched. You may use it to turn ON
an LED lamp and /or a small buzzer to notify a guard; or to energize a relay to switch ON lights or trigger an CCTV
Camera to start recording.
Make sure that the relay for switching ON lights has high enough isolation between high voltage and low voltage
to prevent damage of the keypad.
Only one connection option is recommended. Make sure the sink current does not exceed the maximum rating of
100mA.
External power supply and isolation relay are strictly necessary in driving high power device, such as lights.