User manual

12
10 : DOOR SENS N.C. -- (Door Position Sensing Input -- Normally Close)
A Normally Closed (N.C.) sensing point referring to (
-
) ground, with the help of a normally closed magnetic contact
monitors the open or close state of the door. It initiates the following functions for the system. Connect it with jumper
to (
-
) Ground if not used.
a) Door Auto Re-lock
The system immediately re-locks the door after it is re-closed before the end of the programmed time for output 1.
It prevents unwanted “tailgate” entry.
b) Door Forced Open Warning (available in Split-decoded Mode only)
The controller generates “door forced open” warning and triggers alarm output instantly once the door is forced
to open without using a valid user PIN, Card or pressing of egress button. The warning lasts as long as the
time programmed (1-999 seconds). It can be stopped with the User PIN or card for output 1 at anytime. See
programming Location 80 of the keypad for the details.
c) Door Propped-up Warning (available in Split-decoded Mode only)
The controller generates propped-up warning beeps (does not activates alarm output) while the door is left open
longer than the allowable time programmed. The warning will last as long as the door is open until it is re-closed.
See programming Location 81 of the keypad for the details.
d) Inter-lock Control
The inter-lock control output always goes to (
-
) while the door is open, which gives signal to disable the
associated controller in the inter-lock system. See the Inter-lock terminal description for more information.
e) Door Opening Alarm (available in Split-decoded Mode only)
Door Opening Alarm is designed for the emergency door only. It is always given when the door is opened unless
a valid User Code or Card is used prior to the door is opened. See programming Location 91 of the keypad for the
details.
11 : (
-
) GND -- (Common Ground of The System)
A grounding point of the keypad that is common to terminal 2.
12 : TAMPER IN -- (Tamper Switch – Normally Closed Input Terminal)
A Normally Closed (N.C.) input terminal referring to (
-
) ground. It is prepared for the tamper switch of the keypad
connecting to it. When the tamper switch is open circuit it triggers the internal siren and the Alarm Output terminal.
Link up this terminal to (
-
) Ground with jumper if not used.
The alarm lasts for 3 minute in stand alone mode. It is reset-able before expiry with User Code from keypad in Split-
decoded mode.
13 - 14 - 15 : OUTPUT 1 -- (Output Relay 1)
5 Amp relay dry contact controlled by the Group 1 User PINs & Cards in Split-decoded mode or by the RF remote
key in Stand Alone mode. It is recommended for door strike. Terminal 13 is Normally Closed contact (N.C.), terminal
15 is Normally Open contact (N.O.) and terminal 14 is the common point of the two contacts. Use N.C. output for
Fail-safe locking device; and N.O. output for Fail-secure locking device.
(a) The operation of Output 1 is programmable from the keypad in Split-decoded operation (with Function Jumper on
position 1). See programming Location 51 of the keypad for the details.
(b) The Output 1 is selectable for Start/Stop (toggle) mode (with Function Jumper on position 2) or Adjustable
Momentary Timer mode (with Function Jumper on position 3) in Stand Alone mode.
The Adjustable Timer (1-30 seconds) is located on the main circuit board inside the box. See Figure 2.
16 - 17 - 18 : OUTPUT 2 -- (Output Relay 2)
1 Amp relay dry contact controlled by the Group 2 User PINs & Cards in Split-decoded mode or by the RF remote
key in Stand Alone mode. It is an auxiliary output ideally for controlling of security system or automatic operator.
Terminal 16 is Normally Closed contact (N.C.), terminal 18 is Normally Open contact (N.O.) and terminal 17 is the
common point of the two contacts.
(a) The operation of Output 2 is programmable from the keypad in Split-decoded operation (with Function Jumper on
position 1). See programming Location 52 of the keypad for the details.
(b) The Output 2 is always fixed on Start/Stop (toggle) operation with Function Jumper on position 2 or 3 in Stand
Alone mode.
CONFIGURATION OF THE OUTPUT MODES OF OUTPUT 1, 2 AND 3 (Locations 51, 52 & 53)
The three relay outputs of this keypad are programmable for Start/Stop or Timing modes. Apart from the door access
control, alarm arm-disarm control, they are also universal timers for automatic operators in industry with their
99,999 seconds (over 24 hours) programmable timer.
OUTPUT LOCATIONS
51
-- Location for Output 1
52
-- Location for Output 2
53
-- Location for Output 3
OUTPUT MODE & TIMING
0
– Start /Stop Mode (Toggle)
The number 0 sets the output to the Start / Stop mode. The output Starts when an User PIN and/or Card is entered/
read; the output Stops when an User PIN and/or Card is entered/read again.
1
-
99999
Seconds Momentary --- (Default -- Momentary 5 Seconds)
The output can be set in Momentary Mode with the time of 1 second to 99,999 seconds. The output will reset
automatically when the time expires OR it can be RESET manually at anytime with the Super User Code that
operates the desired output before the end of the time.
Example : Reset Output 1 --
#
1
------------- Output 1 resets
Reset Output 2 --
#
2
------------- Output 2 resets
Reset Output 3 --
#
3
------------- Output 3 resets
PERSONAL SAFETY AND SYSTEM LOCK-OUT (Location 60)
SAFETY & LOCK-OUT OPTIONS
The Options are represented by their Mode Numbers in programming. They are described below:
1
--- After 10 successive false Card/User Code trials, the keypad locks during 60 seconds. -- (Default)
2
--- After 10 successive false Card/User Code trials, activates the Duress output to switch to (
-
) ground.
The Duress Output can be released with any user PIN or Card in the User Group 1 or Super User PIN.
5
-
10
--- Selection of after 5 to 10 successive Card/User Code trials, the keypad locks during 15 minutes.
The keypad can be reset to release the lock-out with the “Super User Code” in the following way.
Example : Release the lock-out --
#
9
00
--- Disappearance of all the above lock-out securities.
SUPER USER CODE
SUPER USER CODE
SUPER USER CODE
1 to 2 Digits
LOCK-OUT MODES VALIDATIONLOCATION
60 #
SUPER USER CODE
OUTPUT MODE & TIME VALIDATIONLOCATIONS
51
-
53 0
or
1
-
99999 #
33
MASTER
INDIVIDUAL