User manual
Operation : (while the system is in the operation mode)
#
(a) (b) (c)
a) Put the EM card close to the reader. One-beep confirms the reading and 30 seconds waiting time is given for the
entry of the Duress Code, the Amber LED keeps flashing
b) Key in one of the Duress Codes for the specific output (the Code programmed in “Location 41, 42, or 43” for
Output 1, 2 and 3 respectively)
c) Confirm it with the # key. The specific Output activates in a normal way and the Duress Output also activates to
report Duress Event to an alarm system.
NOTE: The Duress Event can not be reported if the operation mode is EM Card alone. It is required to key in the
Duress Code directly if necessary.
VISITOR CODES (FOR OUTPUT 1 ONLY) (Location 40)
The Visitor Codes are the temporary user codes for operating of the Output 1 (mainly for door strike in access control).
They can be programmed as “One Time Codes” or “Codes with Time Limit”. The Visitor Codes will be cleared
automatically after use if they are one time codes, or, when the allowed time expires.
VISITOR ID
50 Visitor IDs for storing the codes. They are represented by a
Two-digit ID Number of
01
to
50
.
0999
= Clear all the Visitor Codes from Location 40. Please
see the Programming example below for the details.
VALID PERIOD
The codes in this box MUST be two digits and they represent the time of the operation.
00
--- One Time Code
One Time Code has no time limit but it can only be used for ONCE.
It is cleared by the system automatically after use.
01
-
99
--- Time Limit in Hour(s)
The Visitor Code can be set with the valid time limit of 1 Hour to 99 Hours with a
two-digit number of 01 to 99. The visitor code is cleared by the system when
the time limit reaches.
VISITOR CODES
When a new Visitor Code is put in the same Code box, the old code is replaced.
The Visitor Codes can be 4-8 digits for the Manual Mode code entry.
The Visitor Codes MUST be in the same digit length with the Master Code for Auto Mode code entry.
The Visitor Codes can not reset Duress Output.
NOTE: All Visitor Codes will be cleared after power down to prevent extension/confusion of their valid time limit.
EXAMPLES:
Example 1: Set a “One Time Visitor Code” with the number of “1 2 6 8” for the Output 1
40
01
00
1268
#
(a) (b) (c) (d) (e)
(a) Visitor Code Programming, (b) The Visitor ID, (c) An One Time Code, (d) The Visitor Code, (e) Entry Confirmation
Example 2: Set a “Visitor Code” with the number of “1 3 7 8” that is valid for three hours for the Output 1
40
02
03
1378
#
(a) (b) (c) (d) (e)
(a) Visitor Code Programming, (b) The Visitor ID, (c) Valid for 3 Hours, (d) The Visitor Code, (e) Entry Confirmation
Read Card
Duress Code
4-8 DIGITS
40 #
01
-
50
00
or
01
-
99
VISITOR CODE VALIDATIONLOCATION VISITOR ID VALID PERIOD
20
STATUS LED FLASHING ON-OFF DURING STANDBY (Location 73)
STANDBY FLASHING ON-OFF
Some people find the flashing light of the status LED (the amber LED) is annoying during the keypad is on standby,
especially at the night time. The standby flashing can be ON-OFF with the setting here.
1
--- Standby Flashing ON -- (Default)
The Status LED gives Standby Flashing all the time during the keypad is on standby. It also gives all the light
indications showing the operation status of the system.
0
--- Standby Flashing OFF
The Standby Flashing is disabled but it does not affect the system status indications. All the light indications from it
are unchanged.
DOOR FORCED OPEN WARNING & TIMING (Location 80)
DOOR FORCED OPEN WARNING ON-OFF & TIMING
The Door Forced Open Warning function requires a Door Position Sensing switch (usually a magnetic contact) to work
with. Once a Timing Figure is put into the Function Mode box, the warning mode is enabled.
0
--- Door Forced Open Warning OFF – (Default)
1
-
999
--- Door Forced Open Warning & Alarm ON & Timing
The Timing Figure for the Warning can be 1-999 seconds. The keypad generates the door forced open warning
beeps and activates the alarm output (Terminal 13) instantly if the door is forced to open without a valid User PIN/
Card or pressing of the Egress Button. The beeps and alarm will last as long as the time set on the timer and it can
be stopped at anytime with an User PIN/Card in Group 1 before the end of the time.
The Manner of The Door Forced Open Warning:
a) The door is forced to open (without using PIN/Card or Egress Button) – Warning & Alarm
b) The door is opened with PIN/Card – No Warning or Alarm
c) The door is opened with Egress Button – No Warning or Alarm
DOOR PROPPED-UP WARNING & THE DELAY TIME (Location 81)
DOOR PROPPED-UP WARNING ON-OFF & TIMING
If somebody opened the door and it is left open longer than the allowable delay time, the keypad will generate door
propped-up warning until the door is re-closed. There is warning beeps from the keypad only but does not activates
the alarm output.
0
--- Door Propped-up Warning OFF – (Default)
1
-
999
--- Door Propped-up Warning ON & The Delay Time
The Delay Time can be 1 to 999 seconds. It is the time allows the door to open without starting of the warning.
FUNCTION MODES
FUNCTION MODES
VALIDATION
VALIDATION
LOCATION
LOCATION
0
or
1
-
999
0
or
1
-
999
#
#
80
81
FUNCTION MODES VALIDATIONLOCATION
1
or
0 #73
25