b) Function G2 “PROGRAM SETTING”
The desired times and temperatures within which the universal
thermostat activates or deactivates the connected consumer
according to temperature are set here.
For example, you can specify that a temperature of 20.0 °C
applies from 06:00 AM onwards, followed by a temperature of
18.0 °C from 09:00 AM onwards for the rest of the day.
Depending on whether you have selected the heating or cooling
mode in “INSTALL SETTINGS” in the menu, the consumer connected
to the universal thermostat is activated or deactivated accordingly.
The connected consumer (e.g. a fan heater) is activated in the
heating mode if the temperature measured by the tempera-
ture sensor drops below the temperature value you have pro-
grammed.
To avoid too-frequent activation/deactivation processes, the tem-
perature must deviate by the temperature hysteresis set in the
function G9 “SWING SETTING” before the consumer connected to
the universal thermostat is activated (or deactivated).
Example:
Programmed temperature value: 20.0 °C
Temperature hysteresis: 0.5 °C
Activation/deactivation process: At 19.5 °C or 20.5 °C
Up to 7 different times at which the temperature may change
can be programmed per day (displayed as P1....P7) (step width 10
minutes).
For example, you can specify that a temperature of 20.0 °C ap-
plies from 06:00 AM onwards in the rst memory stop “P1” and
a temperature of 18.0 °C from 09:00 AM onwards in the second
memory slot “P2”.
Proceed as follows for programming:
1. After selecting this function G2 “PROGRAM SETTING” and
con rming with “OK” (2), the number(s) for the weekdays or
day blocks ash at the upper display edge.