Operation Manual
59
i) Function G9 “SWING SETTING”
To prevent the connected consumer from switch on/off too often,
the hysteresis can be set in the function G9.
The consumer is only activated when a specifi c deviation from
the target temperature is exceeded or undercut (depending on
operating mode H1 (“HEAT OR COOL”).
• Heating mode (“HEAT”)
Example:
Hysteresis = 0.5 °C, programmed temperature = +20.0 °C
Consumer is activated at <= +19.5 °C
Consumer is deactivated at >= +20.5 °C
• Cooling mode (“COOL”)
Example:
Hysteresis = 0.5 °C, programmed temperature = +20.0 °C
Consumer is activated at <= +20.5 °C
Consumer is deactivated at >= +19.5 °C
Proceed as follows:
1. After selecting this function G9 “SWING SETTING” and con-
fi rming with “OK” (2), the temperature value for setting the
hysteresis fl ashes (basic setting is 0.5 °C).
2. Set the hysteresis value (0.2 °C....2.0 °C).with the buttons
“–” (5) and “+” (6).
3. Confi rm the setting with “OK” (2).
The universal thermostat is then in the previous menu for
selection of functions again.
To leave the menu and return to the regular display, push the
button “MENU” (3), repeatedly if required.
Observe that a low hysteresis value leads to very fre-
quent activation/deactivation of the consumer!