Output Wiring: Lamp wiring for dimming ballasts can differ significantly from non-dimming ballasts and from
other manufacturers dimming ballasts. Take care to connect lamp lead wires as shown on the applicable
ballast diagram. Lamp Seasoning: For optimal performance, fluorescent lamps may require seasoning for up to 12 hours prior to low temperature starting &
low level dimming. Refer to NEMA LSD 23-2002 Lighting Systems Division: Recommended Practice — Lamp Seasoning for Fluorescent Dimming Systems
Wiring Diagrams
Black
White
Black
White
Violet (+)
Grey (-)
Violet (+)
Grey (-)
Red
Red
Red
Red
Blue
Blue
Blue
Blue
LAMP 1
Yel/Blk
Yellow
Yellow
LAMP 1
LAMP 1
ELECTRONIC
BALLAST
ELECTRONIC
BALLAST
LAMP 2
BALLAST
ELECTRONIC
LAMP 1
LAMP 4
LAMP 3
LAMP 2
Yellow/Black
Yellow
Yellow
Red/Black
Red/White
Red
Red/White
Blue
Blue/White
Blue/White
Blue/Black
Grey (-)
Black
White
Violet (+)
Black
White
Black
White
Violet (+)
Grey (-)
Violet (+)
Grey (-)
Red
Red
Red
Red
Blue
Blue
Blue
Blue
LAMP 1
Yel/Blk
Yellow
Yellow
LAMP 1
LAMP 1
ELECTRONIC
BALLAST
ELECTRONIC
BALLAST
LAMP 2
Yel/Blk
Yellow
Yellow
Red/Black
Red/White
Red
Red/White
Blue
LAMP 1
LAMP 3
ELECTRONIC
BALLAST
Black
White
Violet (+)
Grey (-)
LAMP 2
1 lamp
2 lamp
3 lamp
4 lamp
POWERSENSE
T8 DIM
Performance Guide
High Efficiency, T8 Controllable Lighting Systems, UNV (120-277V)
Input Rated Ballast Input System
1
Item OSRAM SYLVANIA Current Lamp Lumens No. of Factor System Mean Power (W) Efficacy
Number Description (AMPS) Type (lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W) BEF
2
50705 QTP 1x32T8/UNV DIM-TC 0.27/0.12 FO32XP 3000 1 0.88 2640 2480 30 30 88 2.93
0.05 150 140 8 8
0.24/0.11 FO30/SS 2850 1 0.88 2510 2360 28 28 90 3.14
0.05 145 135 8 8
0.22/0.10 FO28/SS 2725 1 0.88 2400 2255 25 25 96 3.52
0.05 135 130 8 8
0.20/0.09 FO25/SS 2475 1 0.88 2180 2045 23 23 95 3.83
0.05 125 115 7 7
50707 QTP 2x32T8/UNV DIM-TC 0.51/0.24 FO32XP 3000 2 0.88 5280 4965 59 57 93 1.54
0.05 300 280 14 14
0.48/0.20 FO30/SS 2850 2 0.88 5015 4715 55 53 95 1.66
0.05 285 270 14 14
0.43/0.18 FO28/SS 2725 2 0.88 4795 4510 51 49 98 1.80
0.05 275 255 13 13
0.39/0.16 FO25/SS 2475 2 0.88 4355 4095 45 44 99 2.00
0.05 250 235 13 13
50714 QTP 3x32T8/UNV DIM-TCL 0.73/0.30 FO32XP 3000 3 0.88 7920 7445 87 84 94 1.05
0.05 450 425 20 20
0.68/0.30 FO30/SS 2850 3 0.88 7525 7075 81 78 96 1.13
0.05 430 400 20 20
0.62/0.26 FO28/SS 2725 3 0.88 7195 6760 73 72 100 1.22
0.05 410 385 19 19
0.56/0.24 FO25/SS 2475 3 0.88 6535 6140 67 66 99 1.33
0.05 370 350 19 19
50716 QTP 4x32T8/UNV DIM-TCL 0.96/0.40 FO32XP 3000 4 0.88 10,560 9925 114 110 96 0.80
0.05 600 565 27 27
0.92/0.39 FO30/SS 2850 4 0.88 10,030 9430 107 104 96 0.85
0.05 570 535 26 26
0.82/0.35 FO28/SS 2725 4 0.88 9590 9015 98 95 101 0.93
0.05 545 510 25 25
0.74/0.32 FO25/SS 2475 4 0.88 8710 8190 91 89 98 0.99
0.05 495 465 24 24
Products are all 10-pack. *Striation might occur with SUPERSAVER lamps.
1: System Efficacy calculation based on lowest input power value.
2: Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value).
Starting Method: Programmed Rapid Start
Circuit Type: Series
Lamp Frequency: >40 kHz
Lamp CCF: Less than 1.7
Starting Temp: 50°F/10°C minimum
for OCTRON T8 lamps
Input Voltage: 120-277V, ±10%
Input Frequency: 50/60 Hz
THD: <10% @ Full Output
Power Factor: >98% @ Full Output
UL Listed Class P, Type 1 Outdoor
CSA or C/UL Certified
70°C Max Case Temperature
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
RoHS compliant
3
ANSI C62.41 Cat. A Transient Protection
Remote mounting (Max. wire length from
ballast case to lampholder)
• up to 8ft for full wattage T8s
• no remote mounting for SUPERSAVER
3 Complies with European Union Restriction
of Hazardous Substances Directive (Directive
EC 2002/95)
Specifications
Data based on F32T8
Item Number 50707 QTP 2 x 32T8 / UNV DIM-TC
QUICKTRONIC
Number of Lamps (1, 2, 3, 4)
System Type - DIMMING/Case Size
Line Voltage (120-277V)
Primary Lamp Wattage
System Life / Warranty
QUICKTRONIC products are covered by the
QUICK 60+
®
warranty, a comprehensive
lamp and ballast system warranty. For
additional details, refer to the QUICK 60+
warranty bulletin.
Data based on SYLVANIA OCTRON
®
lamps
shown. QUICKTRONIC
®
POWERSENSE
ballasts are also compatible with other
manufacturers equivalent lamp types that
meet ANSI specifications, including F17,
F25, F32, U-Bend equivalent lamps and
SUPERSAVER lamps.
T8 POWERSENSE
®
High Efficiency
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Control Information
QUICKTRONIC POWERSENSE ballasts are
compatible with a wide range of low voltage
(0-10VDC) and power line fluorescent controllers
available from various manufacturers.
Low Voltage Control Specs: Ballast will source
up to 0.5mA for 0-10VDC control purposes.
May be wired as a Class 1 or Class 2 circuit-
consult Local and National Electrical Codes.
Power Line Control Specs: Specification-
grade fluorescent controls are available
for 120V or 277V operation of controllable
analog electronic fluorescent ballasts.
Controls must be suitably rated for both the
type (e.g. Fluorescent Phasecontrol) and size
(e.g. 600W) of the connected load.