Installation Sheet

TempControl thermostatic mixing valve made from lead
free** metal components. Models 102-700 feature
serviceable integral check stops. Models 900 & 1000
feature removable check stops with union ells (see table 1
for ow rates).
Coordinating Model Numbers
Specification
Modifications (Components Certified Separately)
Warranty
5 Years - for commercial installations.
Refer to www.symmons.com/warranty for complete
warranty information.
Compliance
Note: Append appropriate sufx to model number.
TempControl 7 Series
Operation & Maintenance Manual
7-102, 7-200, 7-400,
7-500, 7-700, 7-900, 7-1000
-NI
-W
Rough nickel finish
Wall mounting bracket
-P
Polished chrome highlight finish
HTA-100
BV-( )
High temp audio/visual alarm system
Volume control shut off valves
T-425-( )
3” bimetal dial thermometer
SV-( )
WHA-1
Solenoid valve
Water hammer arrestor
TF-( )
Tee fittings
Note: Insert proper model number in parenthesis.
Table 1: Flow Rate - gpm (L/min)
Valve Model Min. Flow Rate*
Min. Flow Rate
(per ASSE 1017)
Pressure Differential - psi (kPa)
5 psi
(34 kPa)
10 psi
(69 kPa)
20 psi
(138 kPa)
25 psi
(172 kPa)
30 psi
(207 kPa)
45 psi
(310 kPa)
7-102
0.5 gpm
(1.9 L/min)
0.5 gpm
(1.9 L/min)
1 gpm
(4 L/min)
3 gpm
(11 L/min)
6 gpm
(23 L/min)
7 gpm
27 L/min)
8 gpm
(30 L/min)
11 gpm
(42 L/min)
7-200
0.5 gpm
(1.9 L/min)
5 gpm
(19 L/min)
7 gpm
(27 L/min)
12 gpm
(46 L/min)
18 gpm
(68 L/min)
21 gpm
(80 L/min)
23 gpm
(87 L/min)
27 gpm
(102 L/min)
7-400
0.5 gpm
(1.9 L/min)
9 gpm
(34 L/min)
18 gpm
(68 L/min)
27 gpm
(102 L/min)
37 gpm
(140 L/min)
41 gpm
(155 L/min)
44 gpm
(167 L/min)
53 gpm
(201 L/min)
7-500
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
22 gpm
(83 L/min)
38 gpm
(144 L/min)
50 gpm
(190 L/min)
55 gpm
(209 L/min)
59 gpm
(224 L/min)
70 gpm
(265 L/min)
7-700
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
25 gpm
(95 L/min)
43 gpm
(163 L/min)
57 gpm
(216 L/min)
62 gpm
(235 L/min)
66 gpm
(250 L/min)
77 gpm
(292 L/min)
7-900
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
30 gpm
(114 L/min)
55 gpm
(209 L/min)
76 gpm
(288 L/min)
84 gpm
(318 L/min)
89 gpm
(337 L/min)
104 gpm
(394 L/min)
7-1000
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
38 gpm
(144 L/min)
67 gpm
(254 L/min)
100 gpm
(379 L/min)
111 gpm
(421 L/min)
120 gpm
(455 L/min)
140 gpm
(531 L/min)
*Minimum ow rate when valve is installed at or near the hot water source with recirculated tempered water and continuously operating circulating pump.
**According to US Senate bill S.3874, the term “lead free” is dened as
follows: “not more than a weighted average of 0.25 percent lead when
used with respect to the wetted surfaces of pipes, pipe ttings, plumbing
ttings, and xtures”
Approach temperature:
5°F (2.8°C)
Temperature control range:
70°F - 150°F (21.1°C - 65.6°C)
-ASME A112.18.1/CSA B125.1, CSA B125.3
-ASSE 1017
-NSF/ANSI 61.9, NSF/ANSI 372
7-102 7-200, 7-400
7-500, 7-700
7-900, 7-1000

Summary of content (36 pages)