Installation Sheet

9
Piping Diagrams
Diagram 1
Single Valve Installation at or near Hot Water Source
tempered water main hot supply to system
high temperature hot (if required for laundry, etc.)
cold supply
valve
valve
thermometer
TempControl thermostatic
water controller
hot
water
tank,
heater,
etc.
Diagram 1 INSTALLATION AT OR NEAR THE HOT
WATER SOURCE: TempControl must be positioned
below the hot water tank or heater, well below the high
temperature water line. This procedure creates a heat
trap and protects against hot water migrating through
the controller.
Diagram 2 INSTALLATION WITH RECIRCULATING
TEMPERED WATER AT HOT WATER SOURCE: Temp-
Control must have the return line connected exactly as
shown. This procedure allows the controller to maintain
the set temperature during periods of no draw by (a)
allowing the major volume of return water to supply the
cold inlet of the TempControl and (b) the minor volume
of return water to be reheated and supply the hot inlet
of the TempControl. When there is no water draw on the
plumbing system, no water can be added to the system;
therefore, the “cold” and “hot” supplies to the Temp-
Control must come from within the system as described
below using the ball valve for ne tuning the operation
as outlined in (a) and (b).
Installation
Diagram 3
Remote HI-LOW System Installation with
Recirculating Tempered Water
tempered water to showers, lavatories, etc.
V1 valve
TMV1
V2 valve
TMV2
check
thermometer
circulating pump
ball valve
hot supply
cold supply
tempered water return to cold inlet of heater
thermometer
check
PRV valve
P1 pressure gauge
P2 pressure gauge
Diagram 3 REMOTE HI-LOW INSTALLATION WITH
RECIRCULATING TEMPERED WATER OR HOT WATER
RETURN: TempControl Hi-Low system must have the
return line connected exactly as shown (See Diagram 2
notes).
PRV valve
TMV2
Diagram 4
Remote HI-LOW System Installation with
Recirculating Hot Water
tempered water to showers,
lavatories, etc.
hot water return
hot supply
cold supply
TMV1
thermometer
V1 valve V2 valve
P1 pressure gauge
P2 pressure gauge
Diagram 4 REMOTE HI-LOW INSTALLATION WITH
RECIRCULATING HOT WATER SUPPLY ONLY:
TempControl Hi-Low system must be piped as shown.