User's Manual

Subfloor EZ Node Hardware Installation Guide
Version 1.0
11
Preparing to Install the Subfloor EZ Node Hardware
The SynapSense Field Engineer is responsible for confirming installation readiness and completing
these steps:
1. Assure the following steps are complete:
a. Required software is installed and configured.
b. Gateways are installed and powered on.
c. All products and tools necessary for installation are on site.
2. Verify the receipt of quantities and contents listed on packing/shipping list found in Box 1.
a. Place kits in front of each cabinet number on the kit bag (or as numbered on the printed
MapSense layout).
b. Verify install team has all necessary tools and additional materials to complete installation and
site is ready for installation.
3. For Subfloor EZ Nodes with MAC IDs not yet recorded or scanned, follow these steps:
a. Record the Subfloor EZ Node MAC IDs manually, or capture them using a barcode scanner
and upload them into MapSense.
b. Access the site layout from the MapSense application. Refer to the MapSense User Guide.
c. Add and configure Subfloor EZ Node objects and associated IDs in the data center floor plan.
4. Export the MapSense project *.dlz file from MapSense for viewing in Web Console.
5. Determine where the subfloor sensor routing will be located.
Subfloor EZ Node Placement
The Subfloor EZ Node is to be mounted under the back of the cabinet or adjacent to the floor
penetration inside the cabinet.
The high-pressure diffuser is to be located under the floor.
The temperature sensor is to be located under the floor.