Instructions / Assembly

®
System 1738 Installation Methods 23
Concentric Vent Termination Kit
Concentric Vent
Termination Kits Include:
Dimension (Inches)
A B* C=
Nominal Pipe Size
F G
Material Concentric Kit Item # D E
PVC 2" x 16" 397005 29.0 16.5 3.5 2 2 7.38 1.75
PVC 2" x 28" 397105 41.0 28.0 3.5 2 2 7.38 1.75
PVC 2" x 40" 397125 53.0 40.0 3.5 2 2 7.38 1.75
PVC 3" x 20" 397006 36.1 20.0 4.5 3 3 8.75 2.25
PVC 3" x 32" 397106 48.1 32.0 4.5 3 3 8.75 2.25
PVC 3" x 44" 397116 60.1 44.0 4.5 3 3 8.75 2.25
PVC 4" x 36" 397021 56.0 37.3 6.62 4 4 10.00 3.50
TABLE 5
B* Dimension be may be shortened to a minimum of 12". Inner pipe (item 3)
must remain “F” inches longer than the outer pipe (item 4). Cut pipe ends
square and solvent weld as outlined in this guide.
C= Installation cut out should be at least 1/2" larger than dimension “C”.
DO NOT LENGTHEN THE CONCENTRIC TERMINATION UNITS.
1 Wye - (Concentric)
2 Rain Cap
3 Exhaust Vent Pipe (Inner)
4 Fresh Air Intake Pipe (Outer)
5 Stainless Steel Bolt & Nut
Do NOT mix pipe, fittings, cements, or joining methods
from different manufacturers, this can result in unsafe
conditions and will void the certification and the
product warranty.
WARNING
System 1738 Pipe, Fittings, Termination Kits and Cements
are certified as a system and must be installed as such.
System 1738 PVC concentric termination kits are made
from a UL1738 certified PVC compound and are rated to
a maximum temperature of 149
o
F.
All termination kits must be located and installed in
accordance with the installation instructions found in this
guide and with the local building code and NFPA 54 /
ANSI Z223.1 National Fuel Gas Code.
A
A
B
B
D
D
D
D
C
C
E
E
G
G
1
1
2
2
3
3
4
4
5
5
45º
F
F
Figure 17
Each Kit Contains:
Item Description
Concentric Vent Wye
Exhaust Pipe
Intake Pipe
Rain Cap
Stainless Bolt and Locknut
Concentric Vent Kit Installation Considerations
1. Kits must be securely fastened to structure, to
ensure clearance dimensions are maintained. Refer
to Figures 17 - 20 for installation clearances in
different installation scenarios.
2. Straps are field supplied. Use straps, clamps or
equivalent that will not score or damage the pipe.
Termination support must allow movement as a
result of expansion and contraction.
3. All penetrations must be sealed according to local
building codes. Caulking for side wall terminations
and flashing for roof penetrations are typical. Use
only PVC compatible sealing material. Contact
the Sealant manufacturer for confirmation on
compatibility with PVC.
4. The weight of the concentric kits must be supported
by the clamps/straps and not by the vent system it
connects to.
5. Insulating exhaust piping in unconditioned space
to prevent freezing may be required by the local
building code.
6. The pipe length of the concentric vent kit can be
shortened, provided that the cutting and welding
procedures adhere to the System 1738 guidelines
outlined in this guide.
NOTE: THE PIPE LENGTH OF THE CONCENTRIC VENT
KIT CANNOT BE LENGTHENED.
7. Pipe lengths and/or fittings shall NOT be solvent
welded to the socket of the rain cap in order to divert
or extend the exhaust gas, unless the appliance
manufacture guidelines confirm that the extra length or
the changing in direction will not adversely impact the
flow of flue gas.