Instruction Manual

D200-68-00 1 I56-1144-05R
2100TR Photoelectronic Smoke
Detector with Fixed Heat
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Diameter: 5.5 inches (140 mm)
Height (including mounting bracket): 1.7 inches (43 mm)
Weight: 6.8 oz. (190 g)
Operating Temperature Range 32° to 100°F (0° to 38°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Heat Sensor: 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 8.5 VDC
Maximum: 35 VDC
Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak)
Standby Current: 50
µ
A average, 100
µ
A maximum
Alarm Ratings: 25.5 mA minimum, 100 mA maximum
(Alarm current must be limited to 100mA by the control panel. If used, the RA400Z
Remote Annunciator operates within the specified detector alarm currents.)
Reset Voltage: 1.3 VDC minimum
Reset Time: 0.3 seconds maximum
Start-up Time: 30 seconds maximum (after 60 sec. reset)
EOL Relay: A77-716B, 12/24 VDC
Remote Annunciator Output: 7 mA maximum
Auxiliary Relay Contact Ratings: 1A @ 30 VAC
Resistive Load: 1A @ 30 VDC
Special Considerations: Only one detector can be used per zone.
Figure 1. Wiring diagram for the 2100TR detector:
A78-2336-17
IMPORTANT: OBSERVE POLARITY
Polarity must be observed on the remote annunciator connections.
OPTIONAL CLASS A WIRING
EOL
+
+
A+
A-
NC
C
NO
RA400Z
REMOTE
ANNUNCIATOR
+
P
W
R
A
U
X
UL LISTED
COMPATIBLE
CONTROL
PANEL
INITIATING
LOOP
+
NOTE: ONLY ONE DETECTOR PER ZONE CAN BE USED.
(OPTIONAL)
RELEASING
DEVICE
NC
COMMON
NO

Summary of content (4 pages)