Manual

D200-82-00 1 I56-1237-01R
2112/24AT
Photoelectronic Smoke Detector with
Fixed Heat and Integral Temp-3 Sounder
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Diameter: 5.5 inches (140 mm)
Height (including mounting bracket): 2.05 inches (52 mm)
Weight: 7.5 oz. (210 g)
Operating Temperature Range: 32° to 100°F (0° to 38°C)
Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing
Latching Alarm: Reset by momentary power interruption
Audible Signal: 85 dBA minimum when in alarm or with supply polarity reversed
Heat Sensor: 135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal): 12 or 24 VDC
Minimum: 10 VDC
Maximum: 35 VDC
Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak)
Standby Current: 50
µ
A maximum
Alarm Current: 49 mA typical, 60 mA max. at 12V
57 mA typical, 65 mA max. at 24V
Reset Voltage: 0.8 VDC minimum
Reset Time: 1.0 second maximum
Start-up Time: 30 seconds maximum (after 60 sec. reset)
EOL Relay: A77-716B, 12/24 VDC
Alarm Initiation
Contact Rating, Resistive Load: 1A @ 30 VDC
Special Considerations: Due to the built-in temporal pattern, use this detector only with a non-coded
power supply.
Figure 1. Wiring diagram for the 2112/24AT detector:
A78-2336-14
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained
following NFPA 72 requirements. The detector should be
cleaned at least once a year.
IMPORTANT: OBSERVE POLARITY
As with all sounder models, polarity must be observed on the power connections.
OPTIONAL CLASS A WIRING
EOL RESISTOR
SPECIFIED BY
PANEL
MANUFACTURER
EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V
POWER
TO
DETECTORS
UL LISTED
COMPATIBLE
CONTROL
PANEL
INITIATING
LOOP
+
P
W
R
P
W
R
+
+
A
A
+
+
A
A
ALARM
CONTACT
ALARM
CONTACT
NOT USED
NOT USED