Manual EZ200

Elztrip EZ200
16
GB
Application area
Elztrip EZ200 has two heating panels and is
designed for ceiling heights between 3 and 10
metres.
EZ200 is used in shops, department stores,
exhibition halls, warehouses etc. EZ200 can
be used both for total and supplementary
heating. EZ200 is also suited for spot heating
of parts of the premises.
Protection class: splash-proof design (IP44).
Operation
The panels have an operating temperature of
up to 320 °C and the heat is radiated to cold
surfaces. Heating with radiant heaters is very
energy effecient and a high comfort level is
obtained. Max. surrounding temperature is
+30 °C.
Mounting
Elztrip EZ200 is mounted on the ceiling, on
armature rails, wire or suspended from the
ceiling by means of rods or chains. The units
are intended for permanent installation and
should always be mounted horizontally.
In rooms frequently used, the heater should
be mounted 1.5 to 2 metres above head
height, see Fig. 2. The distance between the
panels should not be more than the height
between panel and floor, i.e ”a” should be less
than ”H”, see Fig. 2. For minimum mounting
distance, see Fig. 3.
Standard fittings (2 pcs) for mounting are
included and are found inside the connection
box.
1 Determine the position of the panel on the
ceiling.
2 Bend the "legs" of the brackets (fig 1.1)
approximately 90° (fig 1.2).
3 Mount the brackets with an internal
distance according to dimensional drawing
page 4, on the ceiling or on a wire (fig 1.3).
When the panel is mounted on a wire put
the bracket on top of wire. Mount the panel
according to fig 1.4, start with one end
and then assemble the other one. Make
sure that the screws are tightened. When
mounting on wire, use clips that prevent
the panel from sliding.
Electrical installation
EZ200 is intended for permanent installation.
The heater(s) should only be wired by a
competent electrician, and in accordance
with existing national regulations. The
appliance should be preceded by a double
pole switch with at least 3 mm breaking
gap. There are two holes with cable glands
Ø20,5 mm on the top of the connection box.
The cable glands used must guarantee the
protection class requirements. Connection
is done via the block terminals. For serial
connection the maximum fuse size is 35A.
Installation and operating instructions
General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The product may only be used as set out in
the assembly and operating instructions. The
guarantee is only valid if the product is used
in the manner intended and in accordance
with the instructions.
Control
When using this product as a local space
heater according to Ecodesign Regulation
(EU) 2015/1188, it must be supplemented
with one of the following approved controls.
Please note that a relaybox RB3 is required
for 400V~ products.
TAP16R, electronic thermostat that
includes:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
TAP16R and SKG30, black bulb sensor that
include:
- Electronic room temperature control plus
week timer
- Room temperature control with open
window detection
- Black bulb sensor
TAP16R and PDK65, presence detector that
include:
- Electronic room temperature control plus
week timer