See www.frico.se for additional calculations.
AGI4500/60 00
12
Output charts water AGI4500WL
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max 5500 32 43 0,21 0,8 44 42 0,53 4,8
AGI4520WL Max 7300 42 39 0,25 1,3 61 43 0,75 10,1
AGI4525WL Max 9100 52 37 0,29 2,1 78 43,5 0,96 18
AGI4530WL Max 10900 62 37 0,35 2,1 94 44 1,15 20
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max 5500 32 46 0,32 1,8 34 36,5 0,41 3
AGI4520WL Max 7300 42 43 0,378 2,9 48 37,6 0,59 6,5
AGI4525WL Max 9100 52 41 0,436 4,3 62 38 0,75 11,7
AGI4530WL Max 10900 62 41 0,52 4,5 74 38 0,9 13
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max 5500 32 50 0,77 9,7 25 31 0,3 1,7
AGI4520WL Max 7300 42 48 0,85 13,5 35 32 0,43 3,7
AGI4525WL Max 9100 51 45 0,83 14,2 46 33 0,55 6,8
AGI4530WL Max 10900 62 46 1,08 18 55 33 0,66 7, 1
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max 5500 - - - - 19 28 0,3 1,7
AGI4520WL Max 7300 42 50 2,01 46,7 29 30 0,34 2,5
AGI4525WL Max 9100 - - - - 35 29,5 0,56 7, 1
AGI4530WL Max 10900 - - - - 45 30 0,53 4,9
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
– = at the current water temperatures and airflows, the air outlet temperature will be less than 35 °C.