Manual AGI4500 AGI6000

AGI4500/60 00
13
Output charts water AGI4500WH
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
Supply water temperature:110 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 110/80 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WH Max 5500 32 49 0,46 0,26 51 45,6 1,52 2,5
AGI4520WH Max 7300 42 44 0,57 0,45 72 47,3 2,14 5,4
AGI4525WH Max 9100 52 40,5 0,67 0,67 93 48,3 2,75 9,5
AGI4530WH Max 10900 62 41 0,8 0,74 111 48,3 3,3 11,0
Supply water temperature:90 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 90/70 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WH Max 5500 31 53,5 0,21 0,7 42 40,5 0,51 3,8
AGI4520WH Max 7300 42 49,5 0,26 1,12 58 41,8 0,72 7, 9
AGI4525WH Max 9100 52 46 0,29 1,58 74 42 0,9 10,4
AGI4530WH Max 10900 63 47 0,36 1,85 90 42,5 1,1 16,1
Supply water temperature:80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WH Max 5500 31 56 1,15 1,54 34 36,3 1,49 2,5
AGI4520WH Max 7300 42 52,5 1,35 2,32 48 37,5 2,11 5,5
AGI4525WH Max 9100 52 49,5 1,5 3,14 62 38,2 2,72 9,7
AGI4530WH Max 10900 63 50 1,83 3,65 74 38,2 3,26 11,1
Supply water temperature:82°C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 82/71 °C
Room temperature: +18 °C
Type Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WH Max 5500 32 42 0,19 0,7 41 40,1 0,91 11,5
AGI4520WH Max 7300 42 39 0,24 1,2 57 41,1 1,27 23,7
AGI4525WH Max 9100 52 36 0,27 1,8 73 41,7 1,62 26,7
AGI4530WH Max 10900 63 37 0,34 2,0 87 41,8 1,95 27,8
See www.frico.se for additional calculations.