Technical data
Ambient temperature 0…60 °C
Storage temperature -25…+65 °C
Protection class IP54
Installation Snap-on
Cable length 2 m
Weight 100 g (24 V AC/DC, 230 V AC), 111 g (24 V AC)
Models
Article Supply voltage Control signal Stroke time Power consumption Force Stroke
Argus-RTAM100-24 24 V AC/DC On/o, NC 3.5 min 1 W. Max. inrush current < 300 mA
during max. 2 min.
100 N 4 mm
Accessories
Article Description
RTA-CASE Adapter case containing an assortment of adapters for testing on site
Adapters for adjustment of Argus-RTAM100-24 to other brands of valves
Brand Type Thread Colour
Siemens / Oventrop VA10 M30 x 1.5 Light grey
TA VA32 M28 x 1.5 Green
Oventrop VA39 M30 x 1.5 White
Cazzaniga VA44H M32 x 1.5 Grey
Honeywell VA50 M30 x 1.5 Dark grey
MMA VA54 M28 x 1.5 Dark blue
Danfoss RAV/L VA59 M30 x 1.5 Light grey
Pettinaroli VA64 M28 x 1.5 Grey
Danfoss RAV VA72 M30 x 1.5 Light grey
Danfoss RA VA78 M30 x 1.5 White
TA / Heimeier VA80 M30 x 1.5 White/grey
CE
Low Voltage Directive (LVD) standards: This product conforms to the requirements of the European Low Voltage Direc-
tive (LVD) 2014/35/EU through product standards EN 60730-1 and EN 60730-2-14.
EMC emissions & immunity standards: This product conforms to the requirements of the EMC Directive 2014/30/EU
through the product standards EN 60730-1 and EN 60730-2-14.