TOPVEX FC CAV CONVERSION 128300
Table Of Contents
4Conguration(Corrigo)
LogontoAdministratorlevelwithpassword3333.
Menulevel1Menulevel2Menulevel3
Temperature
Aircontrol
Timesettings
→Accessright
→Logon
Logoff
Changepassword
→Logon
Enterpassword:3333
Actuallevel:Admin
Inputs/Outputs
ChangeUAI2toSAFpressureinConfiguration/Inputs/Outputs
Menulevel1Menulevel2Menulevel3
Manualauto
Settings
→Configuration
Accessright
→Inputs/Outputs
Sensorsettings
Controlfunction
Fancontrol
AI
AIexp3
DI1
→UI
Menulevel4Menulevel5
UI1:
ChooseAIorDIsign
AIsign:Notused
DIsign:Notused
↓
UI2:→
ChooseAIorDIsign
AIsign:Notused
DIsign:Notused
UAI2:
Sign:SAFpressure
Rawvalue:NaN
Compensation:0.0°C
Fancontrol
SetthefancontroltypeinmenuConfiguration/Fancontrol.
SetthefancontroltoFlowcontrol.
Menulevel1Menulevel2Menulevel3
Manual/Auto
Settings
→Configuration
Accessrights
Sensorsettings
Controlfunction
→Fancontrol
ExtrasequenceY4
Fancontrol
Flowcontrol→
TopvexFC,CAVconversion
Installationinstructions
128300
4
SystemairSverigeAB