TOPVEX FC CAV CONVERSION 128300
Table Of Contents
Sensorsetting.
SettheadjustedworkingrangefortheaddedCAVpressuretransmitterinmenu
Configuration/Sensorsetting.
AdjustSAF(supplyairfan)andEAF(extractairfan)actualpressurerangeat10,0V.
ExampleTopvexFC02:Ifpressuretransmitterissetto0...1000Paset:0,0V:0,0Paand10,0V
:1000,0Pa.Filterfactorisnottobechanged.
Menulevel1Menulevel2Menulevel3
Manual/Auto
Settings
→Configuration
Accessrights
Inputs/Outputs
→Sensorsettings
Controlfunctions
Fancontrol
SAFpressureat0,0V:0,0Pa
10,0V:XXX,XPa
Filterfactor
Aircontrolsetpoint
AdjusttheFlowctrlSAFandFlowctrlEAFsetpoints.
Menulevel1Menulevel2Menulevel3
Runningmode
Temperature
→Aircontrol
Timesettings
FlowctrlSAF→
Actual:m³/h
Setp:m³/h
↓
FlowctrlSAF
Setp1/1:800m³/h
Setp1/2:400m³/h
←
FlowctrlEAF→
Actual:m³/h
Setp:m³/h
↓
FlowctrlEAF
Setp1/1:800m³/h
Setp1/2:400m³/h
5K-factor
Supplyair
Extractair
TopvexFC02
62
55
TopvexFC04
6672
TopvexFC06
140131
TopvexFC,CAVconversion
Installationinstructions
128300
5