IMO(CE) EX 140 180

2
| Safety information
2 Safety information
Danger
Before maintenance, service or repair cut the power supply (all-pole breaker) and the impeller to stop.
Mounted safety equipment must not be removed, bypassed or be disabled!
Cleaning with a damp cloth when the fan is energized can cause electric shock!
The installation instructions are part of the product and should be stored so that it is always available. The manufacturer
of the system or the plant is responsible for the installation and that safety instructions are in harmony with the
requirements.
EX 140A/180A are certified according to Directive 2014/34/EU (ATEX). Fan Category for fans is BV3 quality grade G6.3
according to ISO 14694. The motor rating plate (A, figure 1) shows data for the motor and does not apply for the com-
plete fan. The fan rating plate shows data for the complete fan (B, figure 1). The field of explosion protection is stated
on the fan rating plate (for example Ex de IIC T4). The fan fulfils the requirement for zone 1 but does not separate zones.
Fan may be used in explosive environments for the transport of gas, but not the transport of hot fumes.
The fan is designed for transport of air or explosive atmospheres in Zone 1 and Zone 2. Transport of solids, shares of
solids or mixtures of dust/air is not allowed. The transported air must not corrode the fan housing, fan blades or motor
(aluminium and steel). Rust particles may not occur in the airflow.
Resonance vibrations can occur due to mounted components and should be checked during commissioning.
The fans must not be installed outdoors.
B
C
A
< 40 mm
Fig. 1
A = Motor data
B = Fan data
C = Production label
Installation, electrical connection and commissioning may only be performed by qualified personnel and in accordance
with the requirements and regulations for electrical installations in areas with explosive atmospheres.
Installation, inspection and maintenance in accordance with EN 60079-14/-17 meets the requirements. Fan should be
installed and protected against foreign objects that come in contact with moving parts and may cause sparks.
No moving parts should be accessible after installation (EN ISO 13857).
Inspection and cleaning should be done regularly, cleaning of deposits will prevent imbalance of the impeller. Make
sure that all the details are correctly reassembled after inspection/cleaning (see chapter 8).
Protective earth (PE) must be connected, the external ground wire connection is placed on the motor (figure 1). Electri-
cal connections must be made according to the wiring diagram. When the fan is controlled the current can increase at
regulated voltage, the power must never exceed the rated power, see table 1. Data provided on the rating plate applies
to air with density of 1.2 kg/m
3
.
135371 | A009