Presafe EU Type Examination Cert. 16 ATEX 8598 X Issue4

Presafe 16 ATEX 8598 X
issue 4
This certificate may only be reproduced in its entirety and without any change, schedule included.
DNV Product Assurance AS, Veritasveien 3, 1363 Høvik, Norway, Tel +47 67 57 88 00,
www.dnv.com ICP-4-5-i1-ATEX-f2, rev 1
Page 2 of 3
[13] Schedule
[14] EU-
Type Examination Certificate N
o:
Presafe 16 ATEX 8598 X
Issue 4
[15]
Description of Product
The centrifugal fan consists of Ex certified electric cage motor and fan casing with impeller.
The impeller is mounted directly on the motor shaft and protected by metallic enclosure (“fan casing”)
from the mechanical damage. Fan casing is fixed to motor
through the “mou
n
ting diskby fastening
screws. The el. motors are fully
covered by the
EPT 17 ATEX 2588 X
Issue 2 certificate.
Motors are
equipped with PTC device which shall be connected to
an appropriate protection device
conforming to EN 50495.
Type designation:
EX 140 and EX 180
Models: EX 140A-2, EX 140A-2C, EX 140A-4, EX 140A-4C, EX 180A-4, EX 180A-4C
Electrical Data
(rating) and ambient temperature are specified in Table 1:
Model
Phase
Supply voltage
Tamb
EX 140A-2C 1 220-240VAC 50Hz -
20°C to +60°C
EX 140A-2 3
230VAC (Δ) 50Hz
-
20°C to +60°C
380-
415VAC (Y) 50Hz
EX 140A-4C, EX 180A-4C 1 220-240VAC 50Hz -
20°C to +60°C
220-240VAC 60Hz
EX 140A-4, EX 180A-4 3
230VAC (Δ) 50Hz
-
20°C to +60°C
380-
415VAC (Y) 50Hz
380-
440VAC (Y) 60Hz
Routine tests:
N/A
[16] Report No.: SC274468/04
Project No.: PRJN-274468-2021-PA-NOR
[17]
Specific Conditions of Use
1.
Thermal protectors (PTC) applied in the motor windings shall be connected to an appropriate protection
device conforming to EN 50495
.
2. When the fans are installed in a duct system the degree of prote
ction IP 20 at the inlet and outlet side
acc.
to (EN 60529) shall be fulfilled for the d
uct system. Components which contribute to the enclosure
protection must be of suitable design material and durability.
3. The supply vol
tage must be within the values specified
i
n table 1 in [15]
4
. Flameproof joints are not intended to be repaired.
[18]
Essential Health and Safety Requirements